Table 8: Electrical Data
ZJ078-150 Standard Motor - Without Powered Convenience Outlet
Compressors
(each)
Size
Volt
(Tons)
RLA LRA
MCC
208
9.3
68.0
14.5
230
9.3
68.0
14.5
078
(6.5)
460
4.9
34.0
7.6
575
3.8
28.0
6.0
208
11.9
88.0
18.5
230
11.9
88.0
18.5
090
(7.5)
460
5.2
44.0
8.1
575
4.8
36.0
7.5
208
12.2
88.0
19.0
230
12.2
88.0
19.0
102
(8.5)
460
5.8
44.0
9.0
575
4.4
36.0
5.5
Johnson Controls Unitary Products
OD Fan
Supply
Pwr
Pwr
Motors
Blower
Exh
Conv
(each)
Motor
Motor
Outlet
FLA
FLA
FLA
FLA
2.1
5.2
5.5
0.0
2.1
5.2
5.5
0.0
1.3
2.6
2.2
0.0
0.7
2.0
1.8
0.0
3.0
5.2
5.5
0.0
3.0
5.2
5.5
0.0
1.6
2.6
2.2
0.0
1.4
2.0
1.8
0.0
3.0
6.8
5.5
0.0
3.0
6.8
5.5
0.0
1.6
3.4
2.2
0.0
1.4
2.4
1.8
0.0
Electric Heat Option
Model
kW
Stages Amps
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
1183875-YIM-A-1014
1
MCA
Max Fuse
1
MCA
w/Pwr
Breaker
(Amps)
Exh
Size
(Amps)
(Amps)
30.3
35.8
35
30.3
37.0
35
53.3
60.2
60
69.0
75.8
70
95.0
101.9
100
30.3
35.8
35
33.6
40.4
35
60.6
67.5
70
78.7
85.5
80
108.7
115.6
110
16.1
18.3
20
16.8
19.5
20
30.3
33.1
35
39.3
42.1
40
54.4
57.1
60
11.9
13.7
15
13.3
15.6
15
24.2
26.4
25
31.4
33.6
35
43.4
45.6
45
38.0
43.5
45
38.0
43.5
45
53.3
60.2
60
69.0
75.8
70
95.0
101.9
100
38.0
43.5
45
38.0
43.5
45
60.6
67.5
70
78.7
85.5
80
108.7
115.6
110
17.5
19.7
20
17.5
19.7
20
30.3
33.1
35
39.3
42.1
40
54.4
57.1
60
15.5
17.3
20
15.5
17.3
20
24.2
26.4
25
31.4
33.6
35
43.4
45.6
45
40.3
45.8
50
40.3
45.8
50
55.3
62.2
60
71.0
77.8
80
97.0
103.9
100
40.3
45.8
50
40.3
45.8
50
62.6
69.5
70
80.7
87.5
90
110.7
117.6
125
19.7
21.9
25
19.7
21.9
25
31.3
34.1
35
40.3
43.1
45
55.4
58.1
60
15.0
16.8
15
15.0
16.8
15
24.7
26.9
25
31.9
34.1
35
43.9
46.1
45
2
Max Fuse
/
2
/
3
Breaker
3
Size w/ Pwr
Exh
(Amps)
45
45
70
80
110
45
45
70
90
125
20
20
35
45
60
15
20
30
35
50
50
50
70
80
110
50
50
70
90
125
20
20
35
45
60
20
20
30
35
50
50
50
70
80
110
50
50
70
90
125
25
25
35
45
60
20
20
30
35
50
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zj seriesZj120Zj102Zj090Zj078Zj078-150