ZJ078-150 Hi Static Motor - With Powered Convenience Outlet
Compressors
(each)
Size
Volt
(Tons)
RLA LRA
MCC
208
9.3
68.0
14.5
230
9.3
68.0
14.5
078
(6.5)
460
4.9
34.0
7.6
575
3.8
28.0
6.0
208
11.9
88.0
18.5
230
11.9
88.0
18.5
090
(7.5)
460
5.2
44.0
8.1
575
4.8
36.0
7.5
208
12.2
88.0
19.0
230
12.2
88.0
19.0
102
(8.5)
460
5.8
44.0
9.0
575
4.4
36.0
5.5
Johnson Controls Unitary Products
OD Fan
Supply
Pwr
Pwr
Motors
Blower
Exh
Conv
(each)
Motor
Motor
Outlet
FLA
FLA
FLA
FLA
2.1
6.8
5.5
10.0
2.1
6.8
5.5
10.0
1.3
3.4
2.2
5.0
0.7
2.4
1.8
4.0
3.0
9.6
5.5
10.0
3.0
9.6
5.5
10.0
1.6
4.7
2.2
5.0
1.4
3.6
1.8
4.0
3.0
9.6
5.5
10.0
3.0
9.6
5.5
10.0
1.6
4.7
2.2
5.0
1.4
3.6
1.8
4.0
Electric Heat Option
Model
kW
Stages Amps
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
1183875-YIM-A-1014
1
MCA
Max Fuse
1
MCA
w/Pwr
Breaker
(Amps)
Exh
Size
(Amps)
(Amps)
42.1
47.6
50
44.6
51.5
50
67.8
74.7
70
83.5
90.3
90
109.5
116.4
110
42.1
47.6
50
48.1
54.9
50
75.1
82.0
80
93.2
100.0
100
123.2
130.1
125
22.0
24.2
25
24.0
26.8
25
37.6
40.3
40
46.6
49.3
50
61.6
64.4
70
16.3
18.1
20
18.8
21.1
20
29.7
31.9
30
36.9
39.1
40
48.9
51.1
50
52.4
57.9
60
52.4
57.9
60
71.3
78.2
80
87.0
93.8
90
113.0
119.9
125
52.4
57.9
60
52.4
58.4
60
78.6
85.5
80
96.7
103.5
100
126.7
133.6
150
24.6
26.8
25
25.7
28.4
30
39.2
41.9
40
48.2
51.0
50
63.2
66.0
70
21.1
22.9
25
21.1
22.9
25
31.2
33.4
35
38.4
40.6
40
50.4
52.6
60
53.1
58.6
60
53.1
58.6
60
71.3
78.2
80
87.0
93.8
90
113.0
119.9
125
53.1
58.6
60
53.1
58.6
60
78.6
85.5
80
96.7
103.5
100
126.7
133.6
150
26.0
28.2
30
26.0
28.4
30
39.2
41.9
40
48.2
51.0
50
63.2
66.0
70
20.2
22.0
25
20.3
22.6
25
31.2
33.4
35
38.4
40.6
40
50.4
52.6
60
2
Max Fuse
/
2
/
3
Breaker
3
Size w/ Pwr
Exh
(Amps)
50
60
80
100
125
50
60
90
100
150
25
30
45
50
70
20
25
35
40
60
60
60
80
100
125
60
60
90
110
150
30
30
45
60
70
25
25
35
45
60
70
70
80
100
125
70
70
90
110
150
30
30
45
60
70
25
25
35
45
60
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zj seriesZj120Zj102Zj090Zj078Zj078-150

Table of Contents