WARNING
Failure to follow this warning could result in personal
injury, property damage, or death.
Before performing service or maintenance operations on
unit, always turn off main power switch to unit and install
lock(s) and lockout tag(s). Unit may have more than one
power switch. Ensure electrical service to rooftop unit
agrees with voltage an amperage listed on the unit rating
plate.
If any wiring changes are required, first be sure to re-
move power from the Economizer module before starting
work. Pay particular attention to verifying the power con-
nection (24 Vac).
Power Up — After the W7220 module is mounted and wired,
apply power.
Initial Menu Display — On initial start up, Honeywell dis-
plays on the first line and economizer W7220 on the second
line. After a brief pause, the revision of the software appears on
the first line and the second line will be blank.
Power Loss (Outage or Brownout) — All setpoints and ad-
vanced settings are restored after any power loss or interrup-
tion.
NOTE: All settings are stored in non-volatile flash memory.
Status — Use the Status menu (see Table 6) to check the pa-
rameter values for the various devices and sensors configured.
NOTE: For information about menu navigation and use of the
keypad see Interface Overview on page 37.
Checkout Tests — Use the Checkout menu (on page 42) to
test the damper operation and any configured outputs. Only
items that are configured are shown in the Checkout menu.
NOTE: For information about menu navigation and use of
the keypad see Interface Overview on page 37.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using
the ▲ and ▼ buttons.
2. Press the
button to select the item.
3. RUN? appears.
4. Press the
button to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all desired parameters have been tested, press the
(Menu Up) button to end the test.
The Checkout tests can all be performed at the time of in-
stallation or at any time during the operation of the system as a
test that the system is operable.
TROUBLESHOOTING
Alarms — The economizer module provides alarm messages
that display on the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before
checking for alarms. This allows time for all the configured
devices (e.g. sensors, actuator) to become operational. The
exception is the SAT sensor which will alarm immediately.
If one or more alarms are present and there has been no key-
pad activity for at least 5 minutes, the Alarms menu displays
and cycles through the active alarms.
You can also navigate to the Alarms menu at any time.
Clearing Alarms — Once the alarm has been identified and
the cause has been removed (e.g. replaced faulty sensor) the
alarm can be cleared from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the
button.
3. ERASE? displays.
4. Press the
button.
5. ALARM ERASED displays.
6. Press the (Menu up/Exit) button to complete the action
and return to the previous menu.
NOTE: If the alarm still exists after you clear it, it is redis-
played within 5 seconds.
Failure to follow this caution may result in damage to
equipment. Be sure to allow enough time for compressor
startup and shutdown between checkout tests so that you
do not short-cycle the compressors.
RTU Open Controller System —
troller is factory-mounted in the 558J unit's main control box
(see Fig. 69), to the left of the CTB. Factory wiring is complet-
ed through harnesses connected to the CTB. Field-connections
for RTU Open controller sensors will be made at the Phoenix
connectors on the RTU Open board. The factory-installed RTU
Open controller includes the supply-air temperature (SAT) sen-
sor. The outdoor air temperature (OAT) sensor is included in
the FIOP/accessory EconoMi$er
The RTU Open controller is an integrated component of the
Bryant rooftop unit. Its internal application programming pro-
vides optimum performance and energy efficiency. RTU Open
enables the unit to run in 100% stand-alone control mode or a
Third Party Building Automation System (BAS). On-board
DIP switches allow you to select your protocol (and baud rate)
of choice among the four most popular protocols in use today:
BACnet*, Modbus†, Johnson N2 and LonWorks**. (See Fig.
68.)
Refer to Table 18, RTU Open Controller Inputs and Outputs
for locations of all connections to the RTU Open controller
board.
NOTE: The RTU Open controller acts as an intelligent imbed-
ded thermostat. A room thermostat cannot be used with the
RTU Open controller.
*
BACnet is a registered trademark of ASHRAE (American
Society of Heating, Refrigerating and Air-Conditioning Engineers).
Modbus is a registered trademark of Schneider Electric.
**
LonWorks is a registered trademark of Echelon Corporation.
48
CAUTION
The RTU Open con-
®
2 package.

Advertisement

Table of Contents
loading

Table of Contents