High Level Signals (Level H); Medium-Power Signals (Level Mp); High-Power Signals (Level Hp); 4.2.3. Cable Spacing Guidelines - GE IC3645SR7A353T3 Installation And Operation Manual

Separately excited (sx) transistorized motor controllers for neighborhood electric vehicle applications
Table of Contents

Advertisement

INSTALLATION AND OPERATION
SX TRANSISTOR CONTROL
DC buses feeding sensitive analog or digital
hardware
All wiring connected to components associated with
sensitive analog hardware with less than 5V signals
(for example, potentiometers and tachometers)
Digital tachometers and resolvers
Dash display cabling
RS-232 cabling
Note: Signal inputs to analog and digital blocks should
be run as shielded twisted-pair (for example, inputs from
tachometers, potentiometers, and dash displays).
4.2.2.b High-Level Signals (Level H)
High-level signals are designated as level H. These
signals consist of:
Analog and digital signals greater than 15 V DC and
less than 250 mA
For example, switch inputs connected to battery volts
are examples of level H signals used in drive equipment
cabling.
4.2.2.c Medium-Power Signals (Level MP)
Medium power signals are designated as level MP.
These signals consist of:
DC switching signals greater than 15 V
Signals with currents greater than 250 mA and less
than 10A
The following are specific examples of level MP signals
used in drive equipment cabling:
DC busses less than 10 A
Contactor coils less than 10 A
Machine fields less than 10 A
4.2.2.d. High Power Signals (Level HP)
Power wiring is designated as level HP. This consists of
DC buses and motor wiring with currents greater than 10
A.
The following are specific examples of level HP signals
used in drive equipment cabling:
Motor armature loops
DC outputs 10 A and above
Motor field loops 10 A and above

4.2.3. Cable Spacing Guidelines

Recommended spacing (or clearance) between cables
(or wires) is dependent on the level of the wiring inside
them. For correct level separation when installing cable,
the customer must apply the general guidelines
(section 4.2.3.a), outlined below.

4.2.3.a General Cable Spacing

The following general practices should be used for all
levels of cabling:
All cables and wires of like signal levels and power
levels must be grouped together.
In general, different levels must run in separate wire
bundles, as defined in the different classes,
identified above. Intermixing cannot be allowed,
unless noted by exception.
Interconnecting wire runs should carry a level
designation.
If wires are the same level and same type signal,
group those wires from one location to any other
location together in multiconductor cables or bind
them together with twine or zip-ties.
When unlike signals must cross, cross them in 90°
angles at a maximum spacing. Where it is not
possible to maintain spacing, place a grounded steel
barrier between unlike levels at the crossover point.

4.2.4 Cabling for Vehicle Retrofits

Reducing electrical noise on vehicle retrofits requires
careful planning. Lower and higher levels should never
encircle each other or run parallel for long distances.
It is practical to use existing wire runs or trays as long as
the level spacing (see section 4.2.2) can be maintained
for the full length of the run.
Existing cables are generally of high voltage potential
and noise producing. Therefore, route levels L and H in a
path separate from existing cables, whenever possible.
For level L wiring, use barriers in existing wire runs to
minimize noise potential.
Do not loop level L signal wires around level H, level MP,
or HP wires.

4.2.5 RF Interference

To prevent radio frequency (RF) interference, care
should be taken in routing power cables in the vicinity of
radio-controlled devices.
Section 4.2.6 Suppression
Unless specifically noted otherwise, suppression (for
example, a snubber) is required on all inductive devices
controlled by an output. This suppression minimizes
noise and prevents damage caused by electrical surges.