Page 1
240 VAC POWER SUPPLY Models: MULTI POSITION SUP10-M2301C SUP15-M2301C SUP18-M2301C SUP20-M2301C SUP23-M2301C SUP20-M2301D SUP23-M2301D SUP27-M2301D Caution: Do not tamper with INSTALLER / SERVICE TECHNICIAN: the unit or its controls. Call a qualified service technician. USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND...
Ask the technician installing your furnace to show SAFETY and explain to you the following items: The main disconnect switch or circuit breaker; DANGER, WARNING AND CAUTION The air filter and how to change it (check The words DANGER, WARNING and CAUTION are used to monthly and clean or replace if necessary);...
same position to insure uniform air distribution through the with it. It is also recommended to install the blower door elements. before handling or moving the unit. Refer to Figure 1 for additional details. POSITIONING THE FURNACE Figure 1: Upflow installation WARNING Fire and explosion hazard.
Once the current has stabilized, a reading should be taken and the anticipator adjusted to that value. The SUPREME furnace is completely pre-wired and all field longer heating cycles are desired, the anticipator can be wiring must be connected to the terminal blocks on the unit.
HIGH If the heating and air-cooling speed are the same, the The SUPREME furnace is equipped with a filter frame for the orange wire and the blue wire can be connected on the blower compartment. It must be installed on the outside of same terminal on the motor.
during a call for heat. Refer to the wiring diagrams for the location of the relay (RAcc) on the control panel. Figure 8 : Manual Furnace Controls 2.7.2. Use of a heat pump When using a heat pump, a thermostat with dial fuel option or a fossil fuel kit is required that prevents the operation of the electric elements and the heat pump at the same time.
3.4.2. High limit verification 0.82 x amps. x volts After operating the furnace for at least 15 minutes, restrict Liter/s= ------------------------- the return air supply by blocking the filters or the return air Diff. temperature ˚C register and allow the furnace to shut off on High Limit. The electric heaters must deactivate themselves one by one 3.1 x amps.
FURNACE INFORMATION Model: Serial number: Furnace installation date: Service telephone # - Day: Night: Dealer name and address: START-UP RESULTS Voltage: Total current consumed by the elements: Supply air temperature: Return air temperature: Supply air duct static pressure: Return air duct static pressure: Total pressure: Calculated air flow: Current consumed by the blower motor:...
3 tons 5 tons 1) Select a blower speed that will generate the specified temperature rise 2) Calculated on the basis of Norm C22.2 Nr. 236 Table 4 : Airflow (CFM) - SUPREME with 1/3HP motor Static Pressure Blower Speed MED-LOW...
Table 6: PARTS LIST, Supreme with 1/3 HP and 1 HP motor: SUPxx-M2301C or SUPxx-M2301D ITEM PART # DESCRIPTION COMMENTS B04114-01 HEATING ELEMENT PLATE ASSEMBLY SUP10kw (1/3 HP) Item 12 included B04115-01 HEATING ELEMENT PLATE ASSEMBLY SUP15kw (1/3 HP) Item 12 included...