Function Setting - Fujitsu AirStage AS A014GCEH Series Installation Manual

Indoor unit (wall mounted type)
Hide thumbs Also See for AirStage AS A014GCEH Series:
Table of Contents

Advertisement

• Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to the figure and table below.
DIP switch
"SET3"
DIP switch

6.3. Function setting

Please make this setting after completing all construction works.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "6.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number
number
00 Standard
Filter indica-
01 Longer
11
tor interval
02 Shorter
00 Enable
01 Disable
Filter indica-
13
Display only on
tor action
02
central remote
controller
(Forbidden)
20
(Forbidden)
23
(Forbidden)
24
(Forbidden)
26
(Forbidden)
27
00 Standard
Cool air
01 Adjust (1)
temperature
30
trigger
02 Adjust (2)
00 Standard
01 Adjust (1)
Heat air
02 Adjust (2)
temperature
31
trigger
03 Adjust (3)
00 Enable
Auto restart
40
01 Disable
00 Super low
Follow the
Cool Air
43
setting on
Prevention
01
the remote
controller
00 Start/Stop
Emergency
01
stop
External
46
control
02 Forced stop
00 All
Error report
Display only on
47
target
01
central remote
controller
Follow the
Fan set-
setting on
ting when
00
the remote
cooling
49
controller
thermostat
OFF
01 Stop
DIP switch "SET3"
ON
OFF
SW
SW
SW
SW
1
2
3
4
Custom code
A (Factory
SET3
B
C
setting)
SW1
OFF
ON
OFF
SW2
OFF
OFF
ON
WARNING
Default
Details
Adjust the filter cleaning interval noti-
fication. If the notification is too early,
change to setting 01. If the notifica-
tion is too late, change to setting 02.
Enable or disable the filter indicator.
Setting 02 is for use with a central
remote controller.
Adjust the cool air trigger tempera-
ture. To lower the trigger tem-
perature, use setting 01. To raise the
trigger temperature, use setting 02.
Adjust the heat air trigger tempera-
ture. To lower the trigger temperature
by 6 degrees C, use setting 01. To
lower the trigger temperature by 4
degrees C, use setting 02. To raise
the trigger temperature, use setting
03.
Enable or disable automatic system
restart after a power outage.
Restrain the cold airflow with making
the airflow lower when starting heat-
ing operation. To correspond to the
ventilation, set to 01.
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all re-
frigerant systems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
Change the target for reporting
errors. Errors can either be reported
in all locations, or only on the central
remote controller.
When set to 01, the fan stops when
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type or
3-wire type) and switching its therm-
istor are necessary.
Function
Function
Setting number
number
00
01
02
03
Switching
function for
04
60
external
05
inputs
06
07
08
09
D
(Forbidden)
61
00
ON
(Forbidden)
62
00
ON
00
Auto mode
68
type
01
00 0°C
01 0.5°C
02 1.0°C
03 1.5°C
Deadband
04 2.0°C
69
value
05 2.5°C
06 3.0°C
07 3.5°C
08 4.0°C
09 4.5°C
(Forbidden)
70
00
(Forbidden)
72
00
(Forbidden)
73
00
(Forbidden)
74
00
(Forbidden)
75
00
6.3.1 Indoor unit indicator lamps
OPERATION indicator lamp (green)
Default
Forced ther-
mostat off
Setting is required when connecting
(Forbidden)
a refrigerant-leak detecting device.
(only for J-IIIL series)
Refrigerant
leak detection
Single
Switch the setting method of
setpoint auto
auto mode to single or dual
mode
(cooling/heating).
(traditional)
For heat pump systems, it is
necessary to set the master indoor
Dual setpoint
unit (by wired remote controller).
auto mode
Choose the minimum temperature
between cooling and heating
settings (deadband) for Dual
setpoint auto mode (set in No. 68).
TIMER indicator lamp (orange)
FILTER indicator lamp (red)
Details
En-8