Electrical Wiring; Electrical Requirement - Fujitsu AirStage AS A014GCEH Series Installation Manual

Indoor unit (wall mounted type)
Hide thumbs Also See for AirStage AS A014GCEH Series:
Table of Contents

Advertisement

4.3.3 Pipe connection
When the flare nut is tightened properly by your hand, hold the body side coupling with a
separate spanner, then tighten with a torque wrench.
Be sure to install the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the flare nut cannot tightened smoothly. If the flare
nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the indoor unit pipe until immediately before connect-
ing the connection pipe.
Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as
this would reduce the lifetime of the units.
Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to
tighten the flare nut correctly.
Flare nut
Tightening torque
[mm (in)]
[N·m (kgf·cm)]
6.35 (1/4) dia.
16 to 18 (160 to 180)
9.52 (3/8) dia.
32 to 42 (320 to 420)
12.70 (1/2) dia.
49 to 61 (490 to 610)
15.88 (5/8) dia.
63 to 75 (630 to 750)
19.05 (3/4) dia.
90 to 110 (900 to 1,100)

5. ELECTRICAL WIRING

Electrical work must be performed in accordance with this Manual by a person certified
under the national or regional regulations. Be sure to use a dedicated circuit for the unit.
An insufficient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fire.
Before starting work, check that power is not being supplied to the all units.
Use the included connection cables and power cables or ones specified by the
manufacturer. Improper connections, insufficient insulation, or exceeding the allowable
current can cause electric shock or fire.
For wiring, use the prescribed type of cables, connect them securely, making sure that
there are no external forces of the cables applied to the terminal connections. Improp-
erly connected or secured cables can cause serious accidents such as overheating the
terminals, electric shock, or fire.
Do not modify the power cables, use extension cables, or use any branches in the wir-
ing. Improper connections, insufficient insulation, or exceeding the allowable current can
cause electric shock or fire.
Match the terminal board numbers and connection cable colors with those of the out-
door unit (or RB unit). Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends of
the wiring, can cause a malfunction, electric shock, or fire.
Always fasten the outside covering of the connection cable with the cable clamp. (If the
insulator is chafed, electric discharge may occur.)
Securely install the electrical box cover on the unit. An improperly installed electrical box
cover can cause serious accidents such as electric shock or fire through exposure to
dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
Install an earth leakage breaker. In addition, install the earth leakage breaker so that the
entire AC main power supply is cut off at the same time. Otherwise, electric shock or fire
could result.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Connect the connection cable firmly to the terminal board. Imperfect installation may
cause a fire.
If the supply cable is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
En-5
CAUTION
Tighten with 2 wrenches.
Torque
wrench
Indoor unit pipe
Connection pipe
(Body side)
WARNING
Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
Do not connect power supply cable to the transmission or remote controller terminals,
as this will damage the product.
Never bundle the power supply cable and transmission cable, remote controller cable
together.
Separate these cable by 50 mm or more.
Bundling these cables together will cause miss operation or breakdown.
When handling PCB, static electricity charged in the body may cause malfunction of the
PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor units for more than 10 seconds to discharge static
electricity charged in the body.
Holding
• Do not touch terminals of parts and patterns implemented on PCB.
wrench
Flare

5.1. Electrical requirement

nut
Voltage rating
Operating range
• Select the power cable type and size in accordance with relevant local and national
regulations.
• Specifications for local wiring power cord and branch wiring are in compliance with local
code.
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire
diameter when the wire length is long.
Breaker should be installed at every refrigerant system. Do not use a breaker in a different
refrigerant system.
Refer to the table for the breaker specifications of each installation condition. Perform
the power crossover wiring within the range of the same refrigerant system. When the
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B
below.
A. Current breaker requirements
Model
AS*A012GCEH
AS*A014GCEH
AS*E012GCEH
AS*E014GCEH
If the capacity of connected RB units and indoor units exceeds the upper limit, either add
breakers or use a breaker with a greater capacity.
B. Earth leakage breaker requirements
Breaker capacity
30 mA, 0.1 sec or less
100 mA, 0.1 sec or less
5.1.1 Cable specifi cations
Power supply cable
Transmission cable
Remote controller
cable (2-wire type)
*1: Use shielded cable in accordance with local rules for remote controller cable.
CAUTION
198 to 264 V (50 Hz)
198 to 253 V (60 Hz)
• MCA: Minimum Circuit Ampacity
MCA
MFA
• MFA: Maximum Fuse Ampacity
0.30 A
When the power crossover wiring is done, make it
0.36 A
so that the total of the MCA of the connected RB
20 A
units and indoor units does not exceed the 15 A.
0.30 A
For RB unit MCA, refer to the RB unit installation
0.36 A
manual.
*1: Heat pump type: indoor units,
Maximum connect-
Heat recovery type: indoor units
able "indoor units"
and RB units.
or "indoor units +
*2: If the total number of units con-
RB units" *1
nected to the breaker exceeds 44,
44 or less *2
either add a 30mA breaker, or use
breakers with a greater capacity.
45 to 148
Recommended
Cable type
cable size (mm²)
Type 60245 IEC
2.5
57 or equivalent
LONWORKS
0.33
compatible
cable
Sheathed PVC
0.33 to 1.25
cable *1
230 V
Remark
2 Cable + earth (ground)
22 AWG LEVEL 4 (NEMA)
non-polar 2 core, twisted pair
solid core diameter 0.65 mm
Non-polar 2 core, twisted
pair

Advertisement

Table of Contents
loading

Table of Contents