Control Mode
2-1. Hot adjust mode
The fan controller becomes the hot adjuster mode for the following conditions.
1 When starting the HEAT operation
2 When the temperature adjustment function changes from OFF to ON.
3 When release the HEAT defrosting operation
A: Hot adjust mode starts.
B: 5 minutes have passed since the condition A or the indoor liquid pipe temperature reached 86°F or more.
C: 5 minutes have passed since the condition A or the indoor liquid pipe temperature reached 95°F or more.
D: 2minutes have passed since the condition C.
(Terminating the hot adjust mode)
2-2. Residual heat exclusion mode
When the condition changes the auxiliary heater ON to OFF (temperature adjustment
function, or operation stop, etc.), the indoor fan operates in [Low] mode for 1 minute.
2-3. Thermo-OFF mode
When the temperature adjustment function changes to OFF, the indoor fan operates in
[Extra low].
2-4. Heat defrosting mode
The indoor fan stops.
3. Drain pump
3-1. Drain pump control
1 ON for 3 minutes after the operation mode is switched from COOL or DRY to another
operation mode (FAN).
2
control judges the sensor is in the water.
3-2. Float switch control
• Float switch control judges whether the sensor is in the air or in the water by turning the
4. Vane control
(Up/down vane
When the last setting is [Swing] ··· [Downward D]
change)
When changing the mode from exception of HEAT to HEAT operation
···[Downward D]
(2) Vane position:
(3) Restriction of vane position
1
(The control by the remote controller is temporally invalidated and control by the unit.)
• Thermo-OFF
• Hot adjust [Extra low] mode
• Heat defrost mode
TCHT002
Control Details
Hot adjust mode*
1
[Low]*
3
[Extra Low]*
3
[OFF]*
2
A
B
C
AT···[last setting]
A
Set fan speed by the remote controller
D
24
Remarks
1
*
"STAND BY" will be
displayed during the
hot adjust mode.
2
*
The step change
of A to B will not be
thermo-ON mode
since the HEAT
operation has started.
3
*
The fan speed varies
according to the setting
of DIP SW1-7 and 1-8
as shown in the table
below.
DIP SW 1-8
ON
B to C [Extra Low]
ON
C to D [Low]
B to C [Extra Low]
OFF
Note: Initial setting
• This control is same
for the model without
auxiliary heater.
• Operates as it would in
COOL operation.
OFF
B to C [Low]
C to D [Low]
C to D [Low]