6

MICROPROCESSOR CONTROL

INDOOR UNIT CONTROL
6-1. COOL OPERATION
RETURN SELECT
MENU
HOLD
.
Control Mode
1. Temperature
1-1. Determining temperature adjustment function
adjustment
(Function to prevent restarting for 3 minutes)
function
• Room temperature
• Room temperature
1-2. Anti-freeze control
Condition to detect
When the pipe temperature detection thermistor/liquid (TH22) detects 32°F or less in 16 minutes
from thermo-ON, the anti-freeze control initiates, and the unit enters to the thermo-OFF.
Condition to release
The timer which prevents reactivating is set for 3 minutes, and anti-freeze control is
1 Pipe temperature detection thermistor/liquid (TH22) reaches 50°F or above.
2 The condition of thermo-OFF has been completed by the thermostat.
3 The operation has changed to a mode other than COOLING.
2. Fan
By the remote controller setting (switch of 4 speeds+Auto)
4 speeds + Auto type
When [Auto] is set, fan speed is changed depending on the value of:
T
High
Med2
Med1
Low
TCHT002
<How to operate>
1 Press ON/OFF button.
2 Press [F1] button to display COOL.
3 Press [F2] [F3] button to set the set temperature.
ON
OFF
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display COOL.
3 Press the TEMP. button to set the set temperature.
Control Details
Set temperature + 2°F ···Thermo-ON
Set temperature ···Thermo-OFF
Type
Auto
1.8 F
3.15 F
NOTE: The settable temperature range varies with the model of
outdoor units and remote controller.
NOTE: The set temperature changes 1°F when the
button is pressed one time. Cooling 67 to 87°F
Fan speed notch
5.4 F
⊿T
19
or
Remarks
• The ON/OFF commands
by the indoor unit
thermostatic control
are not an ON/OFF
commands to the
compressor but an
open/close commands
to the linear expansion
valve. (The compressor
stops only when the
thermostatic control
for all the indoor units
connected to the same
outdoor unit turns OFF.)
Continue to the next page