Trane A952V040BU3SB Installation, Operation And Maintenance Manual page 111

Upflow/horizontal and dedicated downflow gas-fired, direct/non-direct vent, 2-stage condensing variable speed furnaces
Table of Contents

Advertisement

DEFINITION:
Flame is sensed when it
should not be.
Install drip leg per
Na onal Fuel Gas
Code and
Installa on
Instruc ons
There are two flame sense pads located on the IFC,
marked "FP". To measure flame current, use a VOM set
to DC volts. Flame current will vary depending on the
type of meter used. Typical flame current ranges from
0.75 – 3.0 micro-amps (0.75 – 3.0 VDC)
A952V-SVX001-1B-EN
05 Fault Code
Is flame seen
with no call for
heat?
NO
Is flame current
YES
present? See
illustra on
Disconnect power to
unit
Turn off gas supply!
Remove gas valve
Are there signs of
moisture or debris in the
inlet gas screen?
YES
Inspect gas supply
for leaks and have
gas supplier check
gas quality
Is there a drip leg installed
NO
on inlet gas piping per
installa on instruc ons?
YES
Using a back-up wrench,
install new gas valve
Check opera on
NO
Replace IFC
YES
Possible Causes:
Flame sense wire shorted to ground
Flame sensor is grounded
NO
T T r r o o u u b b l l e e s s h h o o o o t t i i n n g g
111

Advertisement

Table of Contents
loading

Table of Contents