Trane A952V040BU3SB Installation, Operation And Maintenance Manual page 109

Upflow/horizontal and dedicated downflow gas-fired, direct/non-direct vent, 2-stage condensing variable speed furnaces
Table of Contents

Advertisement

DEFINITION
Limit switches are safety devices
that will open when an abnormal
high temperature has been sensed.
REMOVE ALL JUMPER WIRING TO
SWITCHES!
Under no circumstances, shall these
switches be le jumpered when not
troubleshoo ng.
Verify filters and blower wheels are
clean
Is 24 VAC
measured across
main thermal
limit?
YL49-YL51
YES
Is external sta c
YES
pressure greater
than nameplate?
Correct applica on or
NO
duct issues.
Check opera on
Is heat rise
within
specifica on?
See Nameplate
YES
Is outlet
manifold gas
NO
pressure within
specifica ons?
Correct gas pressure
Check opera on
A952V-SVX001-1B-EN
04 Fault Code
Is blower motor
running?
Are either of the
flame roll-out
switches tripped?
NO
NO
Note:
Furnace will need to be checked in
st
nd
both 1
& 2
stage opera on
Return air
temperature is
above max limit
YES
Is return air
NO
temperature
NO
above 85 F?
YES
Is temperature at
YES
high limit above the
switch se ng?
NO
Replace high limit
switch
See troubleshoo ng for
NO
motor
YES
Check for loose
insula on or other
objects within
furnace air stream
Make sure any temperature
measuring devices
(thermocouples, dial
thermometers) used to
es mate limit temperature are
within ¼ inch of limit disc
T T r r o o u u b b l l e e s s h h o o o o t t i i n n g g
See next page for
addi onal 04 faults
YES
Does motor
con nue to run
during the en re
hea ng cycle?
YES
Is temperature at
reverse flow switch
NO
above
specifica ons?
Replace reverse flow
switch
YES
Increase blower off delay
109