70
CAUTION
Changing device parameters could adversely affect the control of your
process. Put the control loop in Manual/Out of Service before applying
changes. Verify the output before returning the control loop to Auto.
Failure to do so could result in property damage, serious injury, or
death. Ensure all safety precautions and work procedures have been
followed.
To change the values for parameters:
1.Display the parameters for the device.
2.Double-tap the desired parameter.
3.Change the value for the parameter. (Tap HELP to view a description
of the parameter.)
4.Tap OK. Repeat these steps for other parameters as necessary.
5.Tap SEND to commit your changes to the connected device. After
you tap SEND, the modified values are no longer highlighted yellow.
Displaying the status of a block
Different devices have different options associated with them and the
selections on these menus vary accordingly. See your device
documentation for more information on supported menu items.
To display device status:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap the desired block.
4.Double-tap Status. Status parameters appear.
Running methods
Different devices have different methods associated with them, and the
selections on these menus vary accordingly. See your device
documentation for more information on supported menu items.
To run methods:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap the desired block (typically, methods are run in the
transducer block).
4.Double-tap a menu containing methods. The menu option will vary
for each device.
5.Double-tap the type of method you want to run, for example,
calibration or diagnostic. Follow the prompts on the windows to run
the method.
Fieldbus functionality