Download Print this page

Eaton 9SX8KiPM Instruction Manual page 5

Advertisement

Eaton
Supercharger 240 VDC
®
Installation Manual/Manuel d'installation
Recommended upstream protection / Protection amont recommandée
2 poles circuit breaker D curve - 20A
Disjoncteur 2 pôles courbe D - 20A
G N L
US installations only: to reduce the risk of fire, connect only to a circuit provided
with 20A maximum branch circuit overcurrent protection in accordance with the
National Electrical Code, ANSI/NFPA 70.
Recommended battery protection / Protection batterie recommandée
2 poles circuit breaker - 300V - 60A
Disjoncteur 2 pôles - 300V - 60A
(+) (-)
US installations only: to reduce the risk of fire, connect only to a circuit provided
with 60A maximum branch circuit overcurrent protection in accordance with the
National Electrical Code, ANSI/NFPA 70.
Disconnection and overcurrent protection devices shall be provided by others for permanently
connected AC input and DC output circuits.
Les dispositifs de déconnexion et de protection contre les surintensités doivent être fournis par les
tiers pour les circuits d'entrée en régime alternatif et de sortie en régime continu qui sont branchés en
permanence.
Recommended cable cross-sections / Sections de câble recommandées
Terminal
Function
Borne
Fonction
L1
N(L2)
Input AC
+
-
)
(
)
Output DC
(
Copper wire, solid or stranded / Fil de cuivre, plein ou tressé.
L1
N(L2)
Bat -
Bat +
G
Terminal wire size rating
Minimum wire size
Tailles de fil du bornier
Taille minimum de fil
0.5-6 mm
2
(20-10 AWG)
4 mm
2.5-16 mm
(14-6 AWG)
16 mm
2
to Normal AC source
vers la source Normal AC
to battery
vers la batterie
Tightening torque
Couple de serrage
2
(12 AWG) 75°C
10 lb in / 1.13 Nm
(6 AWG) 90°C
10 lb in / 1.13 Nm
2
Copyright © 2013 EATON
All rights reserved.
614-09350-00

Advertisement

loading

This manual is also suitable for:

9px9sx11kipm9px8kpm9px11kpm9px8kipm9px11kipm ... Show all