Download Print this page
Eaton PWHR1234W2FR Instructions Manual

Eaton PWHR1234W2FR Instructions Manual

Internal battery for use with the eaton 9355 (20/30kva) ups
Hide thumbs Also See for PWHR1234W2FR:

Advertisement

Quick Links

Eaton
® ®
Internal Battery Instructions
For use with the Eaton 9355 (20/30kVA) UPS
p/n: 164201708
Revision 03

Advertisement

loading

Summary of Contents for Eaton PWHR1234W2FR

  • Page 1 Eaton ® ® Internal Battery Instructions For use with the Eaton 9355 (20/30kVA) UPS p/n: 164201708 Revision 03...
  • Page 2 National Fire Protection Association, Inc. ERIFLEX and FLEXIBAR are registered trademark of Erico International Corporation. All other trademarks are property of their respective companies. ©Copyright 2007-2020 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 3 2 2 I I n n s s t t a a l l l l a a t t i i o o n n ............................................................5 5 2.1 Battery Type.............................. 5 2.2 Removing and Replacing the UPS Front Door ....................5 2.3 Installing the Internal Batteries ........................6 Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 4 Table of Contents Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 5 • ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury. Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 6 Tout contact avec une partie d'une batterie mise à la terre peut engendrer un choc électrique. La probabilité d'un tel choc sera réduite si de telles masses sont retirées durant l'installation et la maintenance. Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 7 La probabilidad de una descarga de este tipo se reducirá si se eliminan dichas conexiones a tierra durante la instalación y el mantenimiento. Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 8: Special Symbols

    Phillips and Pozidriv are registered trademarks of Phillips Screw Company. ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA.
  • Page 9 B B a a t t t t e e r r y y T T y y p p e e When purchasing UPS cabinets without batteries, only the following types are recommended. Use of any other battery type inside Eaton cabinets will void the product warranty. CAUTION When replacing batteries, use the same manufacturer and part number originally supplied with the cabinet to ensure correct harness fit and terminal landing.
  • Page 10: Installation

    Verify that the UPS battery circuit breaker is in the OFF position (see Figure Remove the 13 M5 bolts from the battery cover panel and remove the panel. Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 11 Remove the two M5 bolts from each of the three retaining bars and move the retaining bars to the side (see Figure Figure 3. Remove the battery retaining bars Remove the battery trays and the tray kit bag containing the jumper wires. Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 12 5. Place the batteries with the connectors at the bottom. Figure 5. Batteries in Tray Back of Tray Front of Tray Connect eight jumper wires between the batteries. Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 13 Connect the long black wire of the battery tray harness to the negative battery terminal at the back of the tray. 10. Tie wrap the wires to the jumper wires in three places using the supplied tie wraps. Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 14 13. Wrap the supplied tape around the batteries, securing the top and bottom trays to the batteries. Verify that the bent sides of the trays are secure under the tape (see Figure Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 15 Battery Tray Top Back of Tray Tape Front of Tray 14. Write the oldest date code from the battery string (from Step 5) on the top tray, see Figure Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 16 16. Load four battery trays into the bottom of the cabinet (see Figure 10). Repeat for the middle and top rows of battery trays. Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 17 18. Connect the factory-installed cabinet wiring harness to the battery tray wiring harnesses, beginning from the top left, as shown in Figure Repeat for the other rows of battery trays. Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 18 Wiring 19. Reinstall the battery cover panel. 20. Refer to the Eaton 9355 UPS (20/30 kVA) Installation and Operation Manual to continue installing the UPS. Otherwise, reinstall the UPS front door. Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA)
  • Page 19 Installation Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA) 164201708—Rev 03...
  • Page 20 16420170803 164201708 03...