1. Self-Diagnosis Function Table
• The outdoor unit maintenance remote controller can be used to check the alarm display.
The number of times that LED 1 and 2 blink on the outdoor unit control PCB can be used to check the alarm display.
(Refer to "Checking the LED 1 and 2 Alarm Display on the Outdoor Unit Control PCB.")
Alarm code
E06
Outdoor unit failed to receive serial communication signals from indoor unit.
E12
Automatic address setting start is prohibited.
E15
Automatic address setting alarm (too few units)
E16
Automatic address setting alarm (too many units)
E20
No indoor units at automatic address setting.
E24
Outdoor unit failed to receive communications from another outdoor unit.
E25
Outdoor unit address setting failure (duplication)
E26
Mismatch in outdoor unit quantity
E29
Outdoor unit failed to receive communication from another outdoor unit.
F04
Compressor 1 discharge temperature sensor trouble
F05
Compressor 2 discharge temperature sensor trouble
F06
Gas temperature sensor trouble at outdoor heat exchanger 1
F07
Liquid temperature sensor trouble at outdoor heat exchanger 1
F08
Outdoor air temperature sensor trouble
F12
Compressor intake temperature sensor trouble
F16
High-pressure sensor trouble
F17
Low-pressure sensor trouble
F23
Gas temperature sensor trouble at outdoor heat exchanger 2
1
F24
Liquid temperature sensor trouble at outdoor heat exchanger 2
F31
Outdoor unit non-volatile memory (EEPROM) trouble
H03
Compressor 1 CT sensor disconnected or short-circuit
H06
Low-pressure trouble
H08
Compressor 1 oil detection sensor (connection) trouble
H11
Constant speed compressor 2 overcurrent alarm
2
H12
Constant speed compressor 2 lock current alarm
H13
Compressor 2 CT sensor disconnected or short-circuit
H15
Compressor 2 discharge temperature sensor disconnected
H27
Compressor 2 lock current alarm
H31
HIC trouble alarm
3
L04
Outdoor unit address duplication
L10
Outdoor unit capacity not set
L17
Outdoor unit model mismatch
P03
Compressor 1 discharge temperature trouble
P04
High-pressure switch activated
P05
Reverse phase (or missing phase) detected, capacity mismatch
4
P14
O
P16
Compressor 1 overcurrent
P17
Compressor 2 discharge temp trouble
P22
Fan motor trouble
P26
Inverter compressor high-frequency overcurrent alarm
P29
Inverter compressor missing phase or lock alarm
5
6
7
sensor is activated.
2
Alarm meaning
5 - 4
Self-Diagnosis Function Table
(DISCH1)
(DISCH2)
(EXG1)
(EXL1)
(AIR TEMP)
(SCT)
(HPS)
(LPS)
(EXG2)
(EXL2)