Terminal designations

Marking
X61, X62, X63,
X64
1
2
X65, X66
1
2
3
Wiring
Use max. 1.5 mm
conductors for the relay outputs. Ground the cable shield at the drive
end to a signal ground terminal. Refer to hardware manual of the drive or
unit for more information.
Do not route signal cables parallel to power cables.
Tighten the digital I/O signal wiring to 0.3 N·m and the relay output
wiring to 0.5 N·m.
Quick guide - FIO-01
Description
Digital inputs or outputs. Drive parameters
select signal type and use in control
program.
DIOx
• Input: 24 V, "0" < 5 V, "1">15 V.
COM
• Output: Current sink is 500 mA. If more
than two digital outputs are used, current
source is 25 mA. Otherwise current source
is 50 mA.
ROxNO
ROxCOM
ROxNC
2
conductors for the digital signals and max. 2.5 mm
Relay outputs:
• max. 240 VAC, 2 A resistive load
• max. 30 VDC, 5 A resistive load
Inbuilt varistors for inductive load
protection.
2