Example PT Settings:
14400/120 Volts:
set the Pt-n value as 1440, Pt-d value as 120, Pt-S value as 10.
138000/69 Volts:
set the Pt-n value as 1380, Pt-d value as 69, Pt-S value as 100.
345000/115 Volts: set the Pt-n value as 3450, Pt-d value as 115, Pt-S value as 100.
345000/69 Volts:
set the Pt-n value as 345, Pt-d value as 69, Pt-S value as 1000.