4 - PHYSICAL AND ELECTRICAL DATA

4.4 - Compressor electrical data

Compressor
06TTW356
06TUW483
06TUW554
06TVW680
06TVW753
06TVW819
06TTA356
06TUA483
06TUA554
06TVA680
06TVA753
06TVA819
(1) Average value at standard Eurovent conditions: evaporator entering/leaving water temperature = 12°C/7°C, condenser entering/leaving water temperature = 30°C/35°C.
(2) Value at maximum capacity and nominal voltage (400 V).
Legend
MHA
- Maximum compressor operating current, limited by the unit (current given for maximum capacity at 360 V).
LRYA
- Locked rotor current for star connection (connection during compressor start-up).
LRDA
- Locked rotor current for delta connection.

4.5 - Compressor usage per circuit (A, B)

30XW-PZE / 30XWHPZE
Units without option 150
06TTW356
06TUW483
06TUW554
06TVW680
06TVW753
06TVW819
Units with option 150
06TTA356
06TUA483
06TUA554
06TVA680
06TVA753
06TVA819
Electrical data notes and operating conditions, 30XW-PZE/30XWHPZE units
• 30XWZE 301 to 651 units have a single power connection point located immediately
upstream of the main disconnect switch.
30XWZE 801 to 1101 units have two connection points located immediately
upstream of the main disconnect switches.
• The control box includes the following standard features:
- One main disconnect switch per circuit
- Starter and motor protection devices for each compressor
- Anti-short cycle protection devices
- Control devices
• Field connections: All connections to the system and the electrical installations
must be in full accordance with all applicable codes.
• The unit is designed and built to ensure conformance with local codes. The
recommendations of European standard EN 60204-1 (corresponds to IEC 60204-1)
(machine safety - electrical machine components - part 1: general regulations) are
specifically taken into account, when designing the electrical equipment.
• Compliance of the installation to 1999/92/CE directive on minimum requirements for
improving the safety and health protection of workers potentially at risk from explosive
atmospheres : The electrical equipment is not designed for compliance to 2014/34/EU
directive for equipment and protective systems intended for use in potentially explosive
atmospheres. The compliance of the building installation with article 3 Prevention of and
protection against explosions shall be achieved by all necessary measures in the
installation for prevention of the formation of explosive atmospheres
Notes:
• Generally the recommendations of IEC 60364 are accepted as compliance with
the requirements of the installation directives. Conformance with EN 60204-1 is
the best means of ensuring compliance with the Machines Directive.
• Annex B of EN 60204 1 describes the electrical characteristics used for the
operation of the machines.
Greyed text does not apply to units equipped with option 330 (Low GWP A1 R-515B refrigerant)
I Max (A)
I Nom (A)
I Max (A)
(1)
(2)
Option 150B
91
138
115
176
129
201
164
235
177
263
194
276
102
171
125
230
138
252
186
321
197
348
213
364
301
401
451
A
-
-
-
A
-
-
-
A
-
-
-
-
-
-
-
-
-
A
-
-
-
A
-
-
-
A
-
-
-
-
-
-
-
-
-
(2)
MHA (A)
LRYA (A)
121
153
303
155
196
414
176
223
414
205
261
587
232
292
587
244
307
587
na
224
388
na
255
587
na
280
587
na
357
629
na
387
629
na
404
629
551
601
651
-
-
-
-
-
-
-
-
-
A
-
-
-
A
-
-
-
A
-
-
-
-
-
-
-
-
-
A
-
-
-
A
-
-
-
A
The operating environment for the units is specified below:
1. Environment
 as classified in EN 60721 (corresponds to IEC 60721):
(1)
- Indoor installation
- Ambient temperature range: minimum temperature +5°C to +42°C, class
AA4
- Altitude: lower than or equal to 2000 m
- Presence of water: class AD2 (possibility of water droplets)
-   P resence of hard solids, class 4S2 (no significant dust present)
- Presence of corrosive and polluting substances, class 4C2 (negligible)
2. Power supply frequency variation: ± 2 Hz.
3. The neutral (N) line must not be connected directly to the unit (if necessary
use a transformer).
4. Overcurrent protection of the power supply conductors is not provided with the
unit.
5. The factory installed disconnect switch(es)/circuit breaker(s) is (are) of a type
suitable for power interruption in accordance with EN 60947-3 (corresponds
to IEC 60947-3).
6. The unit is designed for connection to TN networks (IEC 60364). For IT networks
the earth connection must not be at the network earth. Provide a local earth,
consult competent local organisations to complete the electrical installation.
NOTE: If particular aspects of an actual installation do not conform to the
conditions described above, or if there are other conditions which should be
considered, always contact your local Carrier representative.
(1) The required protection level for this class is IPX1B (according to reference
standard IEC 60529). The unit fulfils this protection condition. In general the 
casings fulfil class IPX3B
Cosine phi
Cosine phi
LRDA (A)
nom.
(1)
945
0,79
1290
0,86
1290
0,87
1828
0,85
1828
0,87
1828
0,89
1210
0,75
1828
0,80
1828
0,81
1919
0,80
1919
0,81
1919
0,83
801
901
1001
-
-
-
AB
-
-
-
AB
B
-
-
A
-
-
-
-
-
-
-
-
-
AB
-
-
-
AB
B
-
-
A
-
-
-
-
-
-
max.
(2)
0,90
0,90
0,90
0,90
0,90
0,90
0,90
0,90
0,90
0,89
0,89
0,89
1101
-
-
-
AB
-
-
-
-
-
AB
-
-
15