10 - MAJOR SYSTEM COMPONENTS AND OPERATION DATA
10.2.2 - Condenser and oil separator
The 30XW-ZE chiller uses a heat exchanger that is a combination
condenser and oil separator. It is mounted below the evaporator.
Discharge  gas  leaves  the  compressor  and  flows  through  an 
external muffler to the oil separator, which is the upper portion of 
the heat exchanger. It enters the top of the separator where oil is
removed, and then flows to the bottom portion of the vessel, where 
gas is condensed and subcooled. One vessel is used to serve
both refrigerant circuits. There is a center tube sheet which
separates the two refrigerant circuits. The tubes are 3/4" or 1"
diameter internally and externally finned copper tubes.
There is just one water circuit with two water passes (one pass 
with option 102C, please refer to chapter 7.5). For the Heat
Machine units the condenser shell can have a polyurethane foam
thermal insulation (option 86) and a water drain and purge.
It has been tested and stamped in accordance with applicable
pressure codes. The maximum standard relative operating
pressure is 2100 kPa for the refrigerant side and 1000 kPa for the
water-side. These pressures can be different depending on the 
code applied. The water connection of the heat exchanger is a
Victaulic connection.
10.2.3 - Economiser function (depending on model)
The economiser function includes a liquid line valve, a filter drier, 
two electronic expansion valves (EXVs), a plate heat exchanger
as well as protection devices.
At the condenser outlet a part of the liquid is expanded via the
secondary EXV in one of the heat exchanger circuits and then
returns as a gas. This expansion permits increase of the liquid
sub-cooling of the rest of the flow that penetrates the evaporator 
via the principal EXV. This permits increasing the cooling capacity
of the system as well as its efficiency.
10.3 - Detection of the air pressurization of the
electrical cabinet
The electrical cabinet is equipped (except units with option 330)
with a function for detection of its air pressurization. It is made of
a differential pressure sensor that provides a signal to a voltage 
relay. This function insures that the cabinet is always pressurized
above 5Pa in order to avoid any ingress of refrigerant inside the
cabinet. It is aimed at stopping the unit or preventing it from starting
if the pressure differential between the inside and the outside of 
the cabinet is lower than the threshold value. This can happen:
- If the cooling fan of the electrical box fails or if the inlet or
exhaust openings are getting fouled
- If the ducting providing fresh air to the cabinet (refer to §1
p6) is too much resistant to air flow or fouled
- If the cabinet is not tight enough (especially mind the power
input plate and cable glands)

10.4 - Electronic expansion valve (EXV)

The EXV is equipped with a stepper motor (2785 to 3690 steps,
depending on the model) that is controlled via the EXV board.
The EXV is also equipped with a sightglass that permits verification 
of the mechanism movement and the presence of the liquid gasket.
Greyed text does not apply to units does not apply to units equipped with option 330 (Low GWP A1 R-515B refrigerant)
26

10.5 - Moisture indicator

Located on the EXV, permits control of the unit charge and
indicates moisture in the circuit. The presence of bubbles in the
sight-glass indicates an insufficient charge or non-condensables 
in the system. The presence of moisture changes the colour of
the indicator paper in the sight-glass.

10.6 - Filter drier

The role of the filter drier is to keep the circuit clean and moisture 
free. The moisture indicator shows, when it is necessary to change
the element. A difference in temperature between the filter inlet 
and outlet shows that the element is dirty.

10.7 - Sensors

The unit uses thermistors to measure the temperature, and
pressure transducers to control and regulate system operation
(see SmartVu
TM
Control IOM for a more detailed explanation).

10.8 - SRMCR high-pressure safety circuit

10.8.1 - General description
The device is equipped with a high pressure safety loop, also
known as safety related measurement control and regulation
system (SRMCR), consisting of
- 2 high pressure switches (HPS) with manual reset located
at the outlet of each compressor:
• A pressure switch type PZH
• A pressure switch type PZHH
- A control relay on the compressor board.
- 2 compressor main contactors
See the wiring diagram and bill of material of the unit for details
of identification and references.
This safety loop is designed according to EN 61508 for :
SIL level (Safety Integrity): 2.
Demand mode: high and low.
Mission Time : 20 years.
Periodic test: The safety loop operation must be tested at least
once a year to maintain its integrity.