Installation options for the 02 series
SEG1
0
SEG7
1
Use of drain pump
SEG13
Use of external
2
SEG19
Individual control of a
3
remote controller
• Even if you set the Use of drain pump (SEG8) option to 0, it is automatically set to 2 (the drain pump is used with 3
minute delay).
• If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to 2
(1000 hours).
• If you set an option to a value that is out of range specified above, the option is automatically set to 0 by default.
• The SEG5 option (Use of central control) is set to 1 (Use) by default. Therefore, you don't need to set the SEG5 option
additionally. Note that even if the central control system is not connected, no errors occur. If you want a specific
indoor unit not to be controlled by the central control system, set the SEG option of that indoor unit to 0 (Disuse).
• The external output of SEG15 is generated via MIM-B14 connection. (Refer to the manual of MIM-B14.)
• If you set the Individual control with remote control (SEG20) option to a value other than 0 to 4, it is automatically set
to 0 (Indoor 1).
• The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models.
COM1
(+)
Outdoor
DC 12V
Outdoor
DC 12 V
Communication
Communication
DB68-11686A-00_IM_DVM 고효율 Wind Free 4way_AA_EN.indd 27
DB68-11686A-00_IM_DVM 고효율 Wind Free 4way_AA_EN.indd 27
SEG2
SEG3
2
Evaporator Drying
SEG8
SEG9
Use of hot water
heater
SEG14
SEG15
Setting the output
of external control /
External heater signal
control
/ Cooling operation
signal / Free Cooling
control signal
SEG20
SEG21
Heating setting
compensation
/ Removing
condensate water in
heating mode
(-)
COM2
L
N
Wire Remote
AC POWER
HOT COIL
Wire Remote
AC
HOT
Controller
Controller
POWER
COIL
SEG4
SEG5
Use of external
room temperature
sensor / Minimizing
Use of central control
fan operation when
thermostat is off
SEG10
SEG11
EEV Step when
-
heating stops
SEG16
SEG17
S-Plasma ion
Buzzer control
SEG22
SEG23
Adjusted EEV step of
stopped unit during
Motion detect sensor
oil return /defrost
mode.
∗ The output of hot coil terminal is AC 220 V / 230 V
(The same as Indoor Unit's input Power)
SEG6
FAN RPM
compensation
SEG12
Dew removal
operation in wind
free mode
SEG18
Hours of filter usage
SEG24
-
27
English