Installation Procedure
(*3) 1: Fan is turned on continually when the hot water heater is turned on,
3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch(MCM-C200) on the outdoor unit and fix
it as cool mode.
(*4) When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact
control will not be output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned off when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch(MCM-C200) on the outdoor unit and fix
it as cool mode.
- If Fan is set to off for cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external
sensor or wired remote controller sensor to detect indoor temperature exactly.
(*5) When indoor unit is in cooling or Dry mode, The output signal is "ON"
(*6) For free cooling control, Economizer controller is required.
(*7) This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only.
If the air conditioner operates the heating mode immediately after finishing the cooling mode, the condensate
water in the drain pan becomes water vapor by the heat of the indoor unit heat exchanger. Since the water vapor
might be condensed on the indoor unit, which may fall into a living space, use this function to get rid of the water
vapor out of the indoor unit by operating the fan (for maximum 20 minutes) even when the indoor unit is turned off
after cooling mode is turned to heating mode
(*8) Soft Off: If no motion is detected for the Soft Off time, the MDS Kit turns off the indoor units.
Then if any motion is detected until the Hard Off time is passed, the MDS Kit restarts the indoor units.
(*9) Hard Off: If no motion is detected for the Hard Off time, the MDS Kit turns hard off the indoor units.
Then although any motion is detected, the MDS Kit does not restart the indoor and outdoor units.
You must manually restart the units with the wired or wireless remote control.
CAUTION
Electronic heater should
Electronic heater should not
be installed
not be installed
Discharge side
Discharge side
Air Flow
Air Flow
30
English
DB68-11686A-00_IM_DVM 고효율 Wind Free 4way_AA_EN.indd 30
DB68-11686A-00_IM_DVM 고효율 Wind Free 4way_AA_EN.indd 30
Suction side
Suction side
Duct Indoor unit
Duct Indoor unit
• Do not install the electronic heater in the flow channel
of the indoor unit fan.
2022-02-14 오전 10:11:34