LOCATION
DIMENSION
48--- in (1219 mm)
18--- in (457 mm)
A
18--- in (457) mm
12--- in (305 mm)
42--- in (1067 mm)
B
36--- in (914 mm)
Special
36--- in (914 mm)
C
18--- in (457 mm)
42--- in (1067 mm)
D
36--- in (914 mm)
Special
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application
planning overhead obstruction or for vertical clearances.

INSTALLATION

Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) (ANSI/NFPA 70) for special installa-
tion requirements.
2. Determine unit location (from project plans) or select
unit location.
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb
or other) that provides for minimum clearances required
for safety (including clearance to combustible surfaces),
unit performance and service access below, around and
above unit as specified in unit drawings. See Fig. 2.
NOTE: Consider also the effect of adjacent units.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof- - covering material when roof curb is used.
6
C
B
CONDITION
Unit disconnect is mounted on panel
No disconnect, convenience outlet option
Recommended service clearance
Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall)
Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)
Check sources of flue products within 10--- ft of unit fresh air intake hood
Side condensate drain is used
Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)
Check for adjacent units or building fresh air intakes within 10---ft (3 m) of this unit's flue outlet
Fig. 2 - - Service Clearance Dimensional Drawing
Specifications are subject to change without notice.
D
A
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto
unit.
Select a unit mounting system that provides adequate
height to allow installation of condensate trap per
requirements. Refer to Step 10 — Install External
Condensate Trap and Line – for required trap dimensions.
Roof Mount —
Check
building
codes
requirements. Unit operating weight is shown in Table 1.
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different
sequences for the steps of unit installation. For example,
on curb- - mounted units, some accessories must be
installed on the unit before the unit is placed on the curb.
Review the following for recommended sequences for
installation steps.
C08337
for
weight
distribution
516 01 3700 00