Key to Phases (Fig. 10, page 16):
Phase
Function
number
LOC
Lockout shutdown phase
OFF
Standby, waiting for heat request
oP
Part 1: request load controller OPEN
Part 2: modulation of fan motor speed toward high-fire
Part 3: high-fire reached
Part 4: request load controller CLOSED
Part 5: modulation of fan motor speed toward low-fire
Part 6: low-fired reached
10
Settling time, fan motor standby speed
21
Safety valve ON, air pressure switch in no-load posi-
tion
Check if POC is closed, fan motor speed is reduced to
0
22
Part 1: fan motor ON
Part 2: specified time air pressure switch
Message (timeout), stabilization of air pressure switch
24
Settling time, fan motor prepurge speed
30
Part 1: prepurge time without flame simulation test
Part 2: prepurge time with flame simulation test
(2.1 seconds)
36
Speed settling time, fan motor ignition load speed
38
Preignition time
40
Postignition time, parameter 257 + 0.3 seconds
42
Flame detection
44
Interval: end of ignition safety time and release of load
controller
72
Speed stabilization time, fan motor postpurge speed
74
Part 1: operation is ended, check if postpurging is pro-
grammed
Part 2: postpurge time
80
Test space is evacuated
81
Atmospheric pressure test
82
Test space is filled
83
Gas pressure test
90
Pressure switch-min open --> safety shutdown
*1
Valve proving, if P241 = 1 after main ON, lockout or
P234 (postpurge time) = 0 second
*2
Valve proving, if P241 = 1 and P234 (postpurge time)
>0 second
20062175
Technical description of the burner
3.8.1
Both lockout reset button and signal lamp are located in the control
panel.
There are 2 diagnostics choices:
1
2
Visual diagnostics:
in normal operation, the different operating states are indicated in
the form of color codes according to the color code table given be-
low (Tab. L).
Indication of operating state
During startup, state indication takes place according to the Tab. L:
Color code table for multicolor signal lamp
State
Waiting time,
other waiting states
Ignition phase,
ignition controlled
Operation, flame o.k.
Operation,
flame not o.k.
Extraneous light on
burner startup
Undervoltage
Fault, alarm
Error code output (see
Error code Tab. AA,
page 44)
Interface diagnostics
Heating request
New program card
Key (Tab. L)
........
Tab. K
18
GB

Indication of diagnostics mode

The lockout reset button (info button) is the key op-
nfo
erating element for resetting the burner control and
for activating/deactivating the diagnostics func-
tions.
Red
The multicolor signal lamp is the key indicating el-
Yellow
ement for visual diagnostics.
Green
LED
Visual diagnostics: Indication of operating state or diagnostics
of cause of fault
Diagnostics: Via BCI to AZL2... display and operating unit
...............................
...............................
...............................
...............................
Steady on
OFF
Color code
Color
OFF
Blinking
yellow
Green
Blinking
green
Green - Red
Yellow - Red
Blinking red
Red flicker
Yellow
Yellow
Yellow - Red
Red
Yellow
Green
Red
light
Tab. L