PSS SB DI16
Technical details
Electrical data
Supply voltage
Tolerance
Power consumtion
Galvanic isolation
Connection type
SafetyBUS p
Transmission rate
Cable runs
Transmission type
Connection
Digital inputs
Number of inputs
Potential isolation
"1" level (high)
"0" level (low)
Input current
Input delay
Pulse suppression
Status indicator
Dedicated test pulses
Number
Output current at "1" signal
Total load capacity
Cable length
14
24 V DC
20 ... 30 V DC including residual ripple
of max. ± 1.2 V
"Supply": 90 mA plus load currents
from the test pulse outputs and load currents
for fibre-optic couplers (25 mA per fibre-
optic coupler);
Yes (optocoupler), between inputs and
SafetyBUS p
Spring-loaded terminals or plug-in screw
connectors
Max. 500 kBit/s
Max. 3500 m
Two-wire differential (3-core cable)
Fibre-optic cabale via fibre-optic coupler
9-pin D-Sub connector
16
Yes, between inputs and SafetyBUS p
+15 ... +30 VDC
-3 ... +5 VDC
Typ. 6 mA
< 1 ms
< 300 µs
Yellow LED
4 (4 terminals per test pulse, can be
configured in pairs as test pulse or 24 VDC
terminals)
Max. 0.5 A per terminal
Max. 0.5 A per terminal pair
between test pulse output and input
max. 200 m