4
Power up the Gateway
Check power requirements in the table below:
Power Requirement for QuickServer External Gateway
QuickServer Family
FS-QS-3X10-F (Typical)
NOTE: These values are 'nominal' and a safety margin should be added to the power supply of the host system.
A safety margin of 25% is recommended.
Apply power to the QuickServer as shown below. Ensure that the power supply used complies with the specifications
provided in Section
10.3
Specifications.
• The gateway accepts 9-30VDC or 24VAC on pins L+ and N-.
◦ Supports both Full-Wave and Half-Wave AC
• Frame GND should be connected to ensure personnel safety and to limit material damages due to electrical faults.
Ground planes are susceptible to transient events that cause sudden surges in current. The frame ground connection
provides a safe and effective path to divert the excess current from the equipment to earth ground.
NOTE: Floating AC Power Supplies are supported.
Current Draw Type
12VDC
250mA
QuickServer Start-up Guide
24VDC/AC
125mA
12