7.6 Water volume and expansion vessel pressure

Notes
(a) 7KH H[SDQVLRQ YHVVHO LV  OLWHU DQG EDU SUHSUHVVXUL]HG
(b) 7RWDO ZDWHU YROXPH RI  OLWHU LV GHIDXOW LI WRWDO ZDWHU LV FKDQJHG EHFDXVH RI LQVWDOODWLRQ FRQGLWLRQ WKH SUH
pressure should be adjusted to secure proper operation. If the indoor unit is located at the highest position,
DGMXVWPHQW LV QRW UHTXLUHG
(c) 0LQLPXP WRWDO ZDWHU YROXPH LV  OLWHU
(d) 7R DGMXVW SUHSUHVVXUH XVH QLWURJHQ JDV E\ FHUWL¿FDWHG LQVWDOOHU

7.7 The method of calculating the charging pressure of expansion vessel

The method of calculating the charging pressure of expansion vessel needed to be adjusted is as follows.
During installation, if the volume of water system has changed, please check if the pre-set pressure of the
expansion vessel needs to be adjusted according to the following formula:
Pg=(H/10+0.3) Bar (H ---the difference between installing location of indoor unit and the highest spot of
water system.)
(QVXUH WKDW WKH YROXPH RI ZDWHU V\VWHP LV ORZHU WKDQ WKH PD[LPXP YROXPH UHTXLUHG LQ WKH DERYH ¿JXUH ,I LW
exceeds the range, the expansion vessel does not meet the installing requirement.
Installation height
difference
7m
> 7m
Installation height difference: the difference between installing location of indoor unit and the highest spot of
ZDWHU V\VWHP LI WKH LQGRRU XQLW LV ORFDWHG DW WKH KLJKHVW SRLQW RI WKH LQVWDOODWLRQWKH LQVWDOODWLRQ KHLJKW GLIIHUHQFH LV
considered 0m.
Example 1: The indoor unit is installed 5m below the outdoor unit and the total volume of the water system is
/5HIHUULQJ WR WKH DERYH ¿JXUH LW LV QRW QHFHVVDU\ WR DGMXVW WKH SUHVVXUH RI WKH H[SDQVLRQ YHVVHO
280L
Adjustment is not necessary
1. Pre-set pressure needs to be
adjusted according to the above
formula.
2. Check if the water volume is lower
than the maximum water volume. (with
KHOS RI WKH DERYH ¿JXUH
19
Air-to-water Heat Pump All in One Versati
Water volume
> 280L
1. Pre-set pressure needs to be
adjusted according to the above
formula.
2. Check if the water volume is lower
than the maximum water volume. (with
KHOS RI WKH DERYH ¿JXUH
The expansion vessel is too small and
adjustment is not available.