T-SERIES
Air Conditioner
t62 Model
INSTRUCTION MANUAL
Rev. H
© 2019 nVent
88047465
P/N 10-1008-239

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the T62 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for nvent T62

  • Page 1 T-SERIES Air Conditioner t62 Model INSTRUCTION MANUAL Rev. H © 2019 nVent 88047465 P/N 10-1008-239...
  • Page 2: Table Of Contents

    F-GAS INFORMATION ..................................13 NOTE: Some of the information in this manual may not apply if a special unit was ordered. If additional drawings for a special unit are necessary, they have been inserted. Contact nVent Equipment Protection if further information is required.
  • Page 3: Receiving The Air Conditioner

    Damage evident upon receipt should be noted on the freight bill. Damage should be brought to the attention of the delivering carrier -- NOT to nVent Equipment Protection -- within 15 days of delivery. Save the carton and packing material and request an inspection. Then file a claim with the delivering carrier.
  • Page 4: Installation Instructions

    HOW TO READ MODEL NUMBERS G150 1. Identifies the type/family of air conditioner and the approximate height (i.e. T62 = Outdoor family about 62” high). 2. This is the air conditioner’s listed capacity in Btu/hr at rated conditions. (i.e. 22 = 22,000 BTU/Hr.
  • Page 5: Dimensional Drawing

    MOUNTING CUTOUT DIMENSIONS NOTE: Dashed lines represent Mounting Gasket kit, 62-1000-50 included. air conditioner Apply gasket to back of air conditioner before mounting to enclosure. CUTOUT INSTRUCTIONS (As viewed from outside of enclosure) © 2019 nVent 88047465 - 5 -...
  • Page 6: Technical Information

    STANDARD AND OPTIONAL COMPONENT OPERATION THERMOSTAT The T62 air conditioner uses a 10-1061-16 thermostat. The thermostat setpoint equals the temperature that the air conditioner turns off. The thermostat has a 10 F differential from setpoint until it calls for cooling or heating. An example of operation is shown below.
  • Page 7: Contactor

    -3.9 57.8 43.6 51.7 318.3 285.2 -1.1 64.7 49.6 54.4 339.9 306.1 72.2 56.2 57.2 362.4 328.2 80.2 63.2 351.4 88.7 70.7 62.8 410.7 375.9 97.8 78.8 65.6 436.5 401.7 12.8 107.5 87.5 © 2019 nVent 88047465 - 7 -...
  • Page 8: Unit Characteristics

    -XXX will be replaced with a three-digit number designating all desired options. Consult the factory for specific model numbers. FUNCTIONAL DATA Evaporator Air In Evaporator Condenser Evaporator Delta Condenser Delta Unit Amps (°F) Pressure (psi) Pressure (psi) (°F) (°F) 65-80 10-12 45-75 175-225 15-25 18-28 80-100 11.5-15 60-100 210-320 15-25 18-28 © 2019 nVent 88047465 - 8 -...
  • Page 9: Wire Diagram

    WIRE DIAGRAM © 2019 nVent 88047465 - 9 -...
  • Page 10: Service Data

    62-1001-03 Compressor 89073502 Contactor, Compressor 89088986 Controller, Head Pressure 10-1106-108 Evaporator Outlet Filter (Optional) 10-1000-01 Filter/Dryer 52-6028-09 Grille, Condenser fan 13-1014-03 Switch, Dual Pressure 52-6104-59 Thermal Expansion Valve 10-1040-46 Transformer 10-1006-143 Thermostat 10-1061-16 © 2019 nVent 88047465 - 10 -...
  • Page 11: Maintenance

    CAUTION Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly deteriorate condenser coils, blowers and motors, etc. Contact nVent Equipment Protection for special recommendations. REFRIGERANT LOSS Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks.
  • Page 12: Trouble Shooting

    (replace control box cover for safety). This will activate the switch in the thermostat. Turn the power on and if both fans and the compressor come on, the thermostat needs to be replaced. © 2019 nVent 88047465 - 12 -...
  • Page 13: Symptoms And Possible Causes

    Short in system Drain plugged Drain tube kinked Getting water in enclosure Enclosure not sealed (allowing humidity in) Mounting gasket damaged For additional technical information (i.e., amp draw, pressures, temperatures) , contact nVent Equipment Protection at 800-896-2665. F-GAS INFORMATION T622226GXXX T622246GXXX Refrigerant Kühlmittel...
  • Page 14 NOTES © 2019 nVent 88047465 - 14 -...
  • Page 15 NOTES © 2019 nVent 88047465 - 15 -...
  • Page 16 Rev. H © 2019 nVent 88047465 P/N 10-1008-239...