Air Filters; Heating System; Heating Cycle Operation; Safety Controls - Trane YZJ150 Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners precedent cooling and gas/electric
Table of Contents

Advertisement

Gas Heat Operation and Maintenance
Notes:
Single zone VAV is designed to be used with a
zone sensor. If a unit is configured for Single
zone VAV operation but connected to a
thermostat, the control will revert to multi-speed
(two-speed) indoor fan control and staged
compressor control. This drastically reduces
the energy savings available with this design.
eFlex™ is designed to be used with a zone
sensor. If a unit is configured for variable speed
compressor operation but is connected to a
thermostat, the control will revert to multi-speed
indoor fan control and staged compressor
control. This drastically reduces the energy
savings available with this design.

Air Filters

Filters are to be used with this unit. Units ship from the
factory with filters installed.
Figure 38. Gas unit overview
RETURN AIR
AIR FILTERS
PRESSURE SWITCH
It is very important to keep the central duct system air filters
clean. Inspect them at least once each month when the
system is in constant operation. (In new homes, check the
filters every week for the first four weeks.) See the following
table for the required filter size(s).
If the unit has disposable type filters, replace them with
new filters of the same type and size. Do not attempt to
clean disposable filters.
Permanent type filters can be cleaned by washing them
with a mild detergent and water. Confirm the filters are
thoroughly dry before reinstalling them in the unit (or duct
system).
It may be necessary to replace permanent filters annually if
washing fails to clean the filter. Use the same type and size
as originally installed.
54
SUPPLY AIR
GAS VALVE
COMPRESSOR
Table 17. Recommended standard filters
Tons
Unit Model Number
YZJ150***(0,A,B)(L,M,H)
12.5
YZJ180***(0,A,B)(L,M,H)
15
YZJ210***(0,A,B)(L,M,H)
17.5
YZJ240***(0,A,B)(L,M,H)
20
YZJ300***(0,A,B)(L,M,H)
25

Heating System

Heating Cycle Operation

The unit heating system is a solid-state electronic ignition
control that lights the furnace burners each time the
thermostat calls for heat. At the end of each heating cycle
the furnace burners are extinguished. This type of system
is called Direct Spark Ignition (DSI).
A normal heating cycle begins when the air temperature
drops below the thermostat setting. The thermostat then
energizes the heating electrical circuit that starts and
controls the furnace burners. Shortly after the burners
ignite the indoor fan starts and circulates warm air through
the conditioned space.
When the air temperature rises to the thermostat setting
the thermostat deenergizes the heating electrical circuit,
which in turn extinguishes the burners. The indoor fan
continues to circulate warm air until most of the heat is
removed from the unit's combustion chamber.

Safety Controls

The unit is equipped with an automatic reset safety limit
control to prevent overheating. When the control
opens, it shuts down the heating electrical circuit until
the unit cools down sufficiently. Inadequate airflow (i.e.,
caused by dirty filters or defective fan motor) may
cause the unit to cycle on and off as the limit trips and
automatically resets. If the unit is cycling on its limit
control, immediately contact a service person for
instructions.
If flames from the burner are not properly drawn into
the heat exchanger, a flame rollout protection control
will open causing the furnace to shut off. The cause
must be investigated by a qualified service person.
If installed, the condensate overflow switch will shut
down the unit before a drain pan overflow occurs.
Filter Size
Qty
(L x W x D)
4
20 x 24 x 2
4
20 x 30 x 2
4
20 x 24 x 2
4
20 x 30 x 2
4
20 x 24 x 2
4
20 x 30 x 2
4
20 x 24 x 2
4
20 x 30 x 2
4
20 x 24 x 2
4
20 x 30 x 2
RT-SVX077B-EN