Trane Thermafit TACW Installation, Operation And Maintenance Manual page 47

Modular magnetic bearing water-cooled centrifugal chiller
Table of Contents

Advertisement

Table 13. BMS listing - BO (continued)
Tag Name
Chiller: Condenser Flow Fault with DPS
Chiller: Evaporator Flow Switch
Chiller: Condenser Flow Switch
Chiller: Evaporator Pump Enable
Chiller: Condenser Pump Enable
Chiller: Low Lift Active Circuit 1
Chiller: Low Lift Active Circuit 2
Chiller: Low Lift Active Circuit 3
Chiller: Low Lift Active Circuit 4
Chiller: Barrel Isolation Circuit 1
Chiller: Barrel Isolation Circuit 2
Chiller: Evaporator Pump1 Fault
Chiller: Evaporator Pump1 Flow Alarm
Chiller: Evaporator Pump2 Fault
Chiller: Evaporator Pump2 Flow Alarm
Chiller: Condenser Pump1 Fault
Chiller: Condenser Pump1 Flow Alarm
Chiller: Condenser Pump2 Fault
Chiller: Condenser Pump2 Flow Alarm
Chiller: At Maximum Capacity
Chiller: No Compressor Available Fault
Note: Chiller control system provides data for up to 6
compressors.
The BMS Listing has the following characteristics:
All values are integers.
Some of the values like temperatures and pressures
have an implied decimal place; this means that a value
of 450 read from the chiller via BMS interface for Chiller
Outlet Temperature, CHIL_OUT_04, means 45.0 °F (in
imperial configuration).
Some values are enumerated integers:
Chiller State:
Figure 32. Chiller state map
Compressor State:
ARTC-SVX007A-EN
Array
Array
Offset
Chiller Faults
4
Chiller Faults
5
Chiller Faults
6
Chiller Faults
7
Chiller Faults
8
Chiller Faults
9
Chiller Faults
10
Chiller Faults
11
Chiller Faults
12
Chiller Faults
13
Chiller Faults
14
Chiller Faults
16
Chiller Faults
17
Chiller Faults
18
Chiller Faults
19
Chiller Faults
20
Chiller Faults
21
Chiller Faults
22
Chiller Faults
23
Chiller Faults
24
Chiller Faults
25
Figure 33. Compressor state map
Table 14. Fan state map
Value
0
1
2
3
Operating Procedures
Object
Object
Modbus
Type
Instance
Address
BO
219
10205
BO
220
10206
BO
221
10207
BO
222
10208
BO
223
10209
BO
224
10210
BO
225
10211
BO
226
10212
BO
227
10213
BO
228
10214
BO
229
10215
BO
230
10217
BO
231
10218
BO
232
10219
BO
233
10220
BO
234
10221
BO
235
10222
BO
236
10223
BO
237
10224
BO
238
10225
BO
239
10226
Fan State Definition
Label
Off
Hand
Ready
FreeCool
47