GENERAL SAFETY INFORMATION

Intended Use

The Macurco RD-6 is a low voltage, dual relay Refrigerant (REF) detector, controller and transducer. The RD-6 has selectable 4-20 mA
output, buzzer and digital display options. It is an electronic detection system used to measure the concentration of refrigerant gas and
provide feedback and automatic exhaust fan control to help reduce refrigerant gas concentrations in industrial refrigeration, cold
storage, warehouses, hockey rinks or other commercial applications. The RD-6 is a low level meter capable of detecting several
refrigerants including R-22, R-134A, R-404A, R-407C and R-410A, and displaying from 0-1,000 ppm of refrigerant gas. The RD-6 is
factory calibrated and 100% tested for proper operation.
List of Warnings and Cautions within these User Instructions
 Each person using this equipment must read and understand the information in these User Instructions before use. Use of this
equipment by untrained or unqualified persons, or use that is not in accordance with these User Instructions, may adversely affect
product performance and result in sickness or death.
 Use only for monitoring the gas which the sensor and instrument are designed to monitor. Failure to do so may result in exposures
to gases not detectable and cause sickness or death. For proper use, see supervisor or User Instructions, or call Technical
Service at 1-877-367-7891.
 This equipment may not function effectively below 0F or above 125F (-18C or above 52C). Using the detector outside of this
temperature range may adversely affect product performance and result in sickness or death.
 This detector helps monitor for the presence and concentration level of a certain specified airborne gas. Misuse may produce an
inaccurate reading, which means that higher levels of the gas being monitored may be present and could result in overexposure
and cause sickness or death. For proper use, see supervisor or User Instructions, or call Technical Service at 1-877-367-7891.
 High voltage terminals (120/240 VAC) are located within this detector, presenting a hazard to service technicians. Only qualified
technicians should open the detector case and service the internal circuits. Ensure power is removed from the detector relays prior
to servicing the unit. Failure to do so may result in sickness or death.
 Do not disassemble unit or attempt to repair or modify any component of this instrument. This instrument contains no user
serviceable parts, and substitution of components may impair product performance and result in sickness or death.
 Using a certified gas with a concentration other than the one listed for this detector when conducting a calibration or calibration
verification test (bump test) will produce inaccurate readings. This means that higher levels of the gas being monitored may be
present and could result in overexposure and cause sickness or death. For proper use, see supervisor or User Instructions, or
call Technical Service at 1-877-367-7891
 The following steps must be performed when conducting a calibration verification test (bump test) to ensure proper performance of
the monitor. Failure to do so may adversely affect product performance and result in sickness or death.
 When performing a calibration verification test (bump test) only use certified calibration gas at the required concentration level.
Do not test with expired calibration gas.
 If the instrument cannot be tested, do not use until the reason can be determined and corrected.
 Do not cover or obstruct display or visual alarm cover.
 Ensure sensor inlets are unobstructed and free of debris
!