HOW TO USE THE REGULATOR
1
22
Display
current temperature,
humidity,
23
Icon
appears when the pre-set
temperature has not been
reached and the given zone
needs heating.
4
3
How to install floor sensor:
podłogowy
REGULATOR REGISTRATION
5
Each room regulator should be registered in a zone. In order to register,
go to the external controller menu and select: (Menu > Fitter's menu
> Main module/Additional modules > Zones > Zone... > Room
sensor > Sensor selection > Wired RS) and press the registration
button on the regulator.
If the registration process has been completed
successfully, the external controller screen will display
a message to confirm whereas the room sensor screen
will display Scs. If the room sensor displays Err, an
error has occurred during the registration process.
NOTE
•
Only one room regulator may be assigned to
each zone.
•
The regulator can serve as a floor sensor. In
order to do this, connect the NTC sensor to the
regulator and activate it by double-clicking the
registration button. After successful activation,
the Scs message will appear on the controller
display. The Err message displayed on the
screen of the room regulator indicates an error in the activation
process. The activated sensor must be registered in the EU-L-12,
EU-ML-12 or EU-L-X WiFi external controller.(Menu > Fitter's
menu > Main module/Additional modules > Zones >
Zone... > Floor heating > Floor sensor > Sensor selection >
Additional sensor > ON).
•
Hold the registration button to display the current software version.
PRE-SET TEMPERATURE
7
The pre-set zone temperature may be adjusted directly from the EU-F-12b
room regulator using the buttons
During inactivity, the current zone temperature is displayed on the
controller screen. Use the buttons
the pre-set temperature has been defined, the setting screen will appear.
Time settings can be changed using the buttons
- for a specific number of hours - click the button
desired number of hours is displayed, e.g. 1h (the pre-set temperature will
apply for 1 hour, and then the previous setting will apply: schedule or
constant temperature Con). In order to confirm, press the Menu button.
- permanently - press the button
temperature will be valid for an indefinite period of time, regardless of the
schedule settings). In order to confirm, press the Menu button.
- if you want the pre-set temperature resulting from the weekly schedule
settings to apply, press the button
In order to confirm, press the Menu button.
display
.3
Menu button
Menu button
- press - change the view from
room temperature to humidity level/
confirmation of settings
- hold - enter the menu
Buttons
.2
- change of the pre-set temperature
- change parameter settings
floor
Czujnik
sensor
floor sensor
registration
.
to change the set value. When
:
until Con is displayed (the pre-set
until OFF appears on the screen.
2
Examples of compatible frames:
TECH Controllers dedicated glass frame - Sinum FG or
Berker - S.1, B.1, B.3, B.7
Jung - AS, A500, A PLUS, A CREATION
Gira- STANDARD 55, E2, EVENT, ESPRIT, PROFIL55, E22
SIEMENS - DELTA LINE, DELTA VITA, DELTA MIRO,
Kopp - ALASKA
SCHNEIDER - SYSTEM M-PLAN, SYSTEM M-ELEGANCE, M-PURE, M-SMART
Before purchasing a given frame, please check the dimensions
carefully as the above list may change!
We recommend purchasing the FG frame, which is
dedicated to regulators manufactured by TECH Controllers.
How to install particular elements:
4
The system uses a terminating connection. Depending on the order in
which the regulators are connected to the external controller (as the first
one or the one in the middle of the regulator's transmission line with
the external controller), set the terminating resistor in the regulator in
the appropriate position. ON turns the resistor on, and 1 is the neutral
position. Detailed information on the terminating connection of the
external controller with the regulators is described in the EU-L-12, EU-
ML-12 and EU-L-X WiFi manuals.
6
Remember the following rules:
- A registered regulator can be deleted (Menu > Fitter's menu > Main
module / additional module > Zones > Zone ... > Room sensor >
Sensor selection > Wired RS) or disabled using the external controller
(by deselecting ON in the sub-menu of a given zone).
- If the user attempts to assign a regulator to the zone to which other
regulator has already been assigned, the first regulator becomes
unregistered and it is replaced by the other one.
- If the user attempts to assign a sensor which has already been assigned
to a different zone, the sensor is unregistered from the first zone and
registered in the new one.
It is possible to set individual pre-set temperature value and weekly
schedule for each room regulator assigned to a given zone. The settings
may be configured both in the external controller menu and via www.
emodul.eu (use the WiFi module). The pre-set temperature may also be
adjusted directly from the room sensor using the buttons
button
8
In order to enter the menu, hold the Menu button. Use the buttons
to switch between menu options. Confirm by pressing the Menu
button.
FLO
1.
- if you press the Menu button, the floor temperature will be
displayed (option available after activating the floor sensor by pressing
the registration button twice).
CAL
2.
- this function enables the user to set the calibration value for the
room sensor and then the floor sensor Flo (if activated). After entering the
Cal function, press the Menu button. Use the buttons
calibration value. Press the Menu button again, appears Flo - floor sensor
calibration function. Press the Menu button and use the buttons
until the
set the calibration value.
LOC
3.
- the function enables the automatic button lock. After selecting
the Loc function, press the Menu button. Then a question is displayed
whether to enable the lock (yes/no). Select by pressing one of the buttons
. Confirm by pressing the Menu button.To unlock the button, hold
the buttons
are unlocked.
To disable the lock, enter the Loc function again and select the no option.
Confirm by pressing the Menu button.
DEF
4.
- this function allows the user to restore factory settings. After
selecting the Def function, press the Menu button. Then a question is
displayed whether to restore the factory settings (yes/no). Select by
pressing one of the buttons
After restoring factory settings, it will be necessary to re-register the
regulator in the external controller.
RET
5.
- exit the menu. Once in the Ret function, press the Menu button
to exit the menu.
INSTALLATION
EU-F-12b
VCC
B
A
terminating resistor
(jumper)
MENU FUNCTIONS
simultaneously. When Loc is displayed, the buttons
. Confirm by pressing the Menu button.
EU-L-12
VCC
B
A
.
to set the
to
Need help?
Do you have a question about the EU-F-12b and is the answer not in the manual?