8.2. Requirements for Equipment Protection Level Ga
Observe the temperature table for the corresponding equipment protection
level in the certificate.
Also observe the maximum permissible ambient temperature stated in the
technical data. Keep to the lower of the two values.
8.3. Requirements for Equipment Protection Level Da
Observe the temperature table for the corresponding equipment protection
level in the certificate.
Also observe the maximum permissible ambient temperature stated in the
technical data. Keep to the lower of the two values.
9. Delivery, Transport, Disposal
Check the packaging and contents for damage.
Check if you have received every item and if the items received are the
ones you ordered.
Keep the original packaging. Always store and transport the device in the
original packaging.
Store the device in a clean and dry environment. The permitted ambient
conditions must be considered, see datasheet.
The device, built-in components, packaging, and any batteries contained
within must be disposed in compliance with the applicable laws and
guidelines of the respective country.
10. Safety-Relevant Technical Data
10.1. Equipment protection level Ga
Type of protection
Intrinsic safety
CE marking
2-0102
Certificates
Appropriate type
CCB10-30GS55-N1...
ATEX certificate
BVS 13 ATEX E 074 X
ATEX marking
1
ATEX standards
EN IEC 60079-0:2018, EN 60079-11:2012
Effective internal
max. 250 nF
capacitance C
i
Effective internal
max. 200 µH
inductance L
i
Maximum permissible
Also observe the maximum permissible
ambient temperature in °C
ambient temperature stated in the general
technical data. Keep to the lower of the two
values.
for ATEX
U
i
T6: 40 °C
T5: 40 °C
T4: 80 °C
T3: 100 °C
T2: 100 °C
T1: 100 °C
10.2. Equipment protection level Da
Type of protection
Intrinsic safety
CE marking
2-0102
Certificates
Appropriate type
CCB10-30GS55-N1-...
ATEX certificate
BVS 13 ATEX E 074 X
ATEX marking
1
ATEX standards
EN IEC 60079-0:2018, EN 60079-11:2012
Effective internal
max. 250 nF
capacitance C
i
Effective internal
max. 200 µH
inductance L
i
Maximum permissible
Also observe the maximum permissible
ambient temperature in °C
ambient temperature stated in the general
technical data. Keep to the lower of the two
values.
U
i
100 °C
/ 2023-07
II 1G Ex ia IIC T1...T6 Ga
= 15 V, I
= 30 mA, P
= 100 mW
i
i
II 1D Ex ia IIIC T
135°C Da
200
= 15 V, I
= 30 mA, P
= 100 mW
i
i