2.5. Optional parts

Description
Wireless Remote
Controller
Wired Remote Con-
troller
Simple Remote Con-
troller
IR Receiver Unit
Remote Sensor Unit
External Control Set

3. GENERAL SPECIFICATIONS

This INSTALLATION MANUAL brie y outlines where and how
to install the air conditioning system. Please read over the
entire set of instructions for the indoor and outdoor units and
make sure all accessory parts listed are with the system be-
fore beginning.

3.1. Type of copper pipe and insulation material

Copper tubing for connecting the outdoor unit to the indoor
unit and insulation material is available for purchase locally.
When you purchase them, please specify the following.
• Deoxidized annealed copper pipe for refrigerant piping as:
Refer to the Installation Manual for the outdoor unit
for description of allowable pipe length and height
difference.
MODEL
7/9/12
1/4 in. (6.35 mm)
18
1/4 in. (6.35 mm)
24
1/4 in. (6.35 mm)
• Use pipe with water-resistant heat insulation.
• All Fujitsu General products are manufactured to metric
units and tolerances. United States customary units are pro-
vided for reference only. In cases where exact dimensions
and tolerances are required, always refer to metric units.
9374342419_02_IM.indb 5
Model No.
Application
For air conditioner
operation
For air conditioner
RXRNNUM
operation
For air conditioner
RXRSNUM
operation
For the wireless
remote controller
Room temperature
sensor
For control input/
output port
CAUTION
Diameter
Liquid Pipe
Gas Pipe
3/8 in. (9.52 mm)
1/2 in. (12.70 mm)
5/8 in. (15.88 mm)
CAUTION
Install heat insulation around both the gas and liquid
pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 248 °F.
(Reverse cycle model only)
In addition, if the humidity level at the installation lo-
cation of the refrigerant piping is expected to exceed
70%, install heat insulation around the refrigerant pip-
ing. If the expected humidity level is 70-80%, use heat
insulation that is 9/16 in. (15 mm) or thicker and if the
expected humidity exceeds 80%, use heat insulation
that is 13/16 in. (20 mm) or thicker.
If heat insulation is used that is not as thick as speci-
fied, condensation may form on the surface of the
insulation. In addition, use heat insulation with heat
conductivity of 0.045 W/(m•K) or less (at 68 °F).

3.2. Additional materials required for installation

A. Refrigeration (armored) tape
B. Insulated staples or clamps for connecting wire (See your
local electrical codes.)
C. Putty
D. Refrigeration lubricant
E. Clamps or saddles to secure refrigerant piping

3.3. Operating range

Cooling/Dry Mode
Temperature
About 64 to 90 °F
Humidity
About 80% or less
Heating Mode
About 60 to 88 °F
En-5