6.2A.2. INSTALL THE FILTERS
• Install the lters to the unit.
AR7/9/12/18: 2 lters
AR24: 3 lters
6.2A.3. DRILLING HOLES FOR BOLTS AND IN-
STALLING THE BOLTS
• Using the installation template, drill holes for bolts (4 holes).
Installation template
7/9/12
A
28-7/8 (734)
9374342419_02_IM.indb 9
Filter (Accessories)
Unit
Filter
Drilling position
for bolts
Air
A
unit: in. (mm)
18
24
36-3/4 (934)
44-5/8 (1134)
6.2A.4. FIX THE UNIT
(1) Hang the unit
• Use hanger bolts of size M8 or M10 (5/16 or 3/8 in.).
Hanger bolt
Nut A (Field
supply)
Washer (Ac-
cessories)
Nut B (Field
supply)
Nut A (Field
supply)
Washer (Ac-
cessories)
Nut B (Field
supply)
*: It might become dif cult to open and shut the Cover /control
box cover when the length exceeds 13/16 in. (20 mm).
(2) Leveling
Base horizontal direction leveling on top of the unit.
Ceiling
Level gauge
OK
Hanger
Hanger bolt
Hanger
Unit
13/16 in.
(20 mm)
length
Cover
PROHIBITED
2015/6/25 10:27:07
En-9