Toshiba MMK-AP0054MHP1-E1 Service Manual page 28

Table of Contents

Advertisement

6-3. Functions at test run
n Cooling/Heating test run check
The test run for cooling/heating can be performed from either indoor remote controller or outdoor interface P .C.
board.
1. Start/Finish operation of test run
¤ Test run from indoor remote controller
Wired remote controller: Refer to the below item of "Test run" of the wired remote controller.
Wireless remote controller: Refer to the next page item of "Test run" of the wireless remote controller.
u In case of wired remote controller
<RBC-AMT32E>
TEMP.
TIMER SET
TIME
FILTER
1,
RESET
TEST
SET
CL
5
Procedure
Push [TEST] button for 4 seconds or more.
1
[TEST] is displayed at the display part and
the mode enters in TEST mode.
2
Push [ON/OFF] button.
Change the mode from [COOL] to [HEAT] using [MODE] button.
• Do not use [MODE] button for other mode except
3
[COOL]/[HEAT] modes.
• The temperature cannot be adjusted during test run.
• The error detection is performed as usual.
4
After test run, push [ON/OFF] button to stop the operation.
(Display on the display part is same to that in Procedure
Push [TEST] button to clear the TEST mode.
5
([TEST] display in the display part disappears and
status becomes the normal stop status.)
Note) The test run returns to the normal operation after 60 minutes.
2,
ON / OFF
4
FAN
MODE
3
SAVE
VENT
SWING/FIX
UNIT LOUVER
<RBC-AMS41E>
TEMP .
FILTER UP/DN
PROGRAM DAY
1,
FLT.RESET TEST
5
Operation contents
1
.)
28
FILE NO. SVM-16045
ON / OFF
SCHEDULE
FAN
MODE
TIME
SAVE
VENT
SET
CL
SWING/FIX
UNIT
LOUVER
TEST
TEST
2,
4
3

Advertisement

Table of Contents
loading

Table of Contents