Toshiba MMK-AP0054MHP1-E1 Service Manual page 108

Table of Contents

Advertisement

SMMS High-Wall Type
2. When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening
without a door, or an opening 0.15 % or larger than the respective floor spaces at the top or bottom of the door).
3. If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the smallest
room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas
leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room
becomes the object.
Very small room
▼ NOTE 3
The minimum indoor floor area compared with the amount of refrigerant is roughly as follows:
(When the ceiling is 2.7 m high)
Important
Refrigerant piping
Medium room
Small
room
Mechanical ventilation device - Gas leak detector
40
Range below the
2
35
m
density limit of
3
0.3 kg/m
30
(countermeasures
not needed)
25
20
15
10
5
0
10
Total amount of refrigerant
Outdoor unit
Refrigerant piping
Indoor unit
Outdoor unit
Indoor unit
Large room
Range above the density
3
limit of 0.3 kg/m
(countermeasures needed)
20
30
109
FILE NO. SVM-16045
Installation Manual
kg