Download Print this page
RCF PLP 50EN User Manual
RCF PLP 50EN User Manual

RCF PLP 50EN User Manual

Flush-mount ceiling loudspeaker in compliance with en 54-24 standard

Advertisement

Available languages

Available languages

Quick Links

PLP 50EN
USER MANUAL
MANUALE D'USO
FLUSH-MOUNT
CEILING LOUDSPEAKER
IN COMPLIANCE WITH
EN 54-24 STANDARD
DIFFUSORE ACUSTICO
PER CONTROSOFFITTO
CONFORME ALLA
NORMA EN 54-24

Advertisement

loading
Need help?

Need help?

Do you have a question about the PLP 50EN and is the answer not in the manual?

Questions and answers

Summary of Contents for RCF PLP 50EN

  • Page 1 USER MANUAL MANUALE D’USO PLP 50EN FLUSH-MOUNT CEILING LOUDSPEAKER IN COMPLIANCE WITH EN 54-24 STANDARD DIFFUSORE ACUSTICO PER CONTROSOFFITTO CONFORME ALLA NORMA EN 54-24...
  • Page 3: Table Of Contents

    TABLE OF CONTENTS INDICE ENGLISH SAFETY AND OPERATING PRECAUTIONS DESCRIPTION INSTALLATION CONNECTION NOTES ABOUT CONSTANT VOLTAGE SYSTEMS SPECIFICATIONS ITALIANO AVVERTENZE PER LA SICUREZZA E PRECAUZIONI D’USO DESCRIZIONE INSTALLAZIONE COLLEGAMENTO NOTE SUI SISTEMI A TENSIONE COSTANTE DATI TECNICI...
  • Page 4 RCF S.p.A. will not assume any responsibility for the incorrect installation and / or use of this product. SAFETY AND OPERATING PRECAUTIONS 1.
  • Page 5 9. RCF S.p.A. strongly recommends this product is only installed by professional qualified installers (or specialised firms) who can ensure a correct installation and certify it according to the regulations in force. The entire audio system must comply with the current standards and regulations regarding electrical systems.
  • Page 6: Description

    HAS BEEN DESIGNED TO GUARANTEE RELIABILITY AND HIGH PERFORMANCE. DESCRIPTION The PLP 50EN ceiling loudspeaker is in compliance with EN 54-24 standard. It is equipped with a plastic fire dome and can be installed flush-mounted in false ceilings or panels.
  • Page 7 1. Drill a hole of diameter 151 mm (5.94”) in the false ceiling panel, as shown in figure 1. ø 151 FIGURE 1 2. Loosen the bolt of the fire dome, which needs to be removed to access all internal parts. Make the electrical connection as described in the next section of the manual, set the desired power...
  • Page 8: Connection

    CONNECTION WARNING: loudspeAkeR coNNectIoNs should be oNly MAde by quAlIfIed ANd expeRIeNced peRsoNNel hAvING the techNIcAl kNoW hoW oR suffIcIeNt specIfIc INstRuctIoNs to eNsuRe thAt coNNectIoNs ARe MAde coRRectly ANd to pReveNt ANy electRIcAl dANGeR o pReveNt ANy RIsk of electRIc shock do Not coNNect loudspeAkeRs WheN the AMplIfIeR Is sWItched oN efoRe tuRNING the systeM oN...
  • Page 9 TRANSFORMER POWER SELECTION Link the ‘TAP’ connector (red wire) to the transformer contact having the desired power value (see the next table and the figure 4). POWER POWER (pins) (100 V) (70 V) 1.5 W 0.75 W 1.5 W FIGURE 4...
  • Page 10 NOTES ABOUT CONSTANT VOLTAGE SYSTEMS - The loudspeaker input voltage (Vd) shall correspond to the amplifier output voltage (Va). - The sum of nominal power values (Pd x n) of all loudspeakers connected to the line shall not exceed the amplifier power (Pa). - Make sure all loudspeakers are connected in phase to ensure a correct sound reproduction.
  • Page 11: Specifications

    SPECIFICATIONS Input voltage: 100 V ( / 70 V) Power (selectable) at 100V: 6 W – 3 W – 1.5 W (power values are halved at 70 V) Input impedance: 1.67 kΩ – 3.33 kΩ – 6.67 kΩ Frequency response: 130 Hz ÷...
  • Page 12 L’installazione e l’utilizzo errati del prodotto esimono la RCF S.p.A. da ogni responsabilità. AVVERTENZE PER LA SICUREZZA E PRECAUZIONI D’USO 1.
  • Page 13 9. La RCF S.p.A. raccomanda vivamente che l’installazione di questo prodotto sia eseguita solamente da installatori professionali qualificati (oppure da ditte specializzate) in grado di farla correttamente e certificarla in accordo con le normative vigenti.
  • Page 14: Descrizione

    REALIZZATO IN MODO DA GARANTIRNE L’AFFIDABILITÀ E PRESTAZIONI ELEVATE. DESCRIZIONE PLP 50EN è un diffusore acustico a plafoniera conforme alla norma EN 54- 24 e provvisto di fondello antifiamma in plastica, installabile ad incasso in controsoffittature o pannelli. E’ particolarmente indicato per la diffusione di messaggi di allarme: la sua caratteristica principale è...
  • Page 15 1. Praticare nella controsoffittatura un foro del diametro di 151 mm, come indicato in figura 1. ø 151 FIGURA 1 2. Svitare il bullone del fondello, il quale va rimosso per accedere alle parti interne. Effettuare il collegamento elettrico come descritto nella successiva sezione del manuale;...
  • Page 16: Collegamento

    COLLEGAMENTO AtteNzIoNe: peR Il colleGAMeNto del dIffusoRe sI RAccoMANdA dI RIvolGeRsI A peRsoNAle quAlIfIcAto ed AddestRAto ossIA peRsoNAle AveNte coNosceNze tecNIche o espeRIeNzA o IstRuzIoNI specIfIche suffIcIeNtI peR peRMetteRGlI dI ReAlIzzARe coRRettAMeNte le coNNessIoNI e ’ pReveNIRe I peRIcolI dell elettRIcItà...
  • Page 17 IMPOSTAZIONE DELLA POTENZA SUL TRAFORMATORE Collegare il connettore “TAP” (filo rosso) al contatto del trasformatore di linea avente la potenza desiderata (vedere la seguente tabella e la figura 4). POTENZA POTENZA (contatti) (100 V) (70 V) 1,5 W 0,75 W 1,5 W FIGURA 4...
  • Page 18 NOTE SUI SISTEMI A TENSIONE COSTANTE - La tensione d’ingresso del diffusore (Vd) deve corrispondere con la tensione d’uscita dell’amplificatore (Va). - La somma delle potenze nominali di tutti i diffusori (Pd x n) collegati alla linea non deve superare quella dell’amplificatore (Pa). - Per garantire una corretta riproduzione audio, effettuare il collegamento di tutti i diffusori “in fase”.
  • Page 19: Dati Tecnici

    DATI TECNICI Tensione d’ingresso: 100 V ( / 70 V) Potenza (selezionabile) a 100 V: 6 W – 3 W – 1,5 W (i valori sono dimezzati a 70 V) Impedenza d’ingresso: 1,67 kΩ – 3,33 kΩ – 6,67 kΩ Risposta in frequenza: 130 Hz ÷...
  • Page 20 Salvo eventuali errori ed omissioni. RCF S.p.A. si riserva il diritto di apportare modifiche senza preavviso. Except possible errors and omissions. RCF S.p.A. reserves the right to make modifications without prior notice. www.rcf.it RCF S.p.A. Italy Via Raffaello Sanzio, 13...