Technical Data; Electrical Connection - M&C 70304 Instruction Manual

Table of Contents

Advertisement

10

TECHNICAL DATA

Temperatue controller
type
Part No.
Temperature sensor
Logic output
Switching capacity solid state relais
Control mode
Status alarm
Indicators
Temperatures
Climatic conditions
Electrical connections
Power supply
Housing material
Housing version
Weight / Protection
Optional: Controller with mA-
outlet for actual value
11

ELECTRICAL CONNECTION

Warning
Note
www.mc-techgroup.com
70304
01B8401
Resistance thermometer, thermocouple
0/12 V DC, max. 30 mA
to an external solid state relay
external
PID
High temperature limiter with continious cutoff, low temperature alarm: 1 contact
NO each, potential free, contact rating 250 V AC, 3 A
Measuring temperature: 4 digits 7 Seg LED red 10 mm; setting value: as listed before
but 7.0 mm; ON operation, ramp function on, 2 alarms
Ambient 0 -55 °C; storage -30 to +70 °C
< 90% r.H., dew not allowed
Terminals 1.5 mm
2
110-240 V +10/-15 %, 48-63 Hz, 8 VA
Synthetic material
Front panel mounting
200 g /
terminals IP20,
housing IP 20, front
plate IP 65 EN60529
01B8411
An incorrect system voltage can damage the unit. When establishing electri-
cal connection, ensure that the system voltage corresponds to the voltage
specified on the rating plate!
For the erection of power installations with rated voltages up to 1000V, the
requirements of VDE 0100 and relevant standards and specifications must be
observed! The supply circuit of the unit must be provided with a fuse of 16 AT
(time-delay fuse, overcurrent protection); the electrical values are shown in the
technical data.
Temperature controller 70304 | 1.02.00
70304.2
01B8456
Ambient 0 -50 °C; storage -30 to +70 °C
Rail mounting
320 g / IP20 EN 60529
01B8457
11