Treatment Of Measurement Errors - Vega VEGAPULS C 23 Operating Instructions Manual

Radar sensor for continuous level measurement of liquids
Hide thumbs Also See for VEGAPULS C 23:
Table of Contents

Advertisement

Code
Text message
S601
Overfilling
S603
Impermissible operating
voltage
Maintenance
Code
Text message
M500
Error in the delivery
status
M501
Error in the delivery
status
M504
Error at a device inter-
face
M505
No echo available
M507
Error in the instrument
settings
M508
Data error in program
memory Bluetooth con-
troller
M509
Software update
M510
No communication with
the sensor
VEGAPULS C 23 • SDI-12
Cause
Danger of vessel overfilling
Terminal voltage too small
Cause
Hardware defect
Sensor does not detect an echo during
operation
Antenna dirty or defective
Error during setup
Error when carrying out a reset
False signal suppression faulty

10.4 Treatment of measurement errors

The tables below give typical examples of application-related meas-
urement errors.
The images in column "Error description" show the actual level as a
dashed line and the output level as a solid line.
10 Diagnostics and servicing
Rectification
Make sure that there is no further filling
Check level in the vessel
Check terminal voltage, increase operat-
ing voltage
Rectification
Check connections
Exchanging the electronics
Send instrument for repair
Clean the antenna
Use a more suitable antenna/sensor
Remove possible false echoes
Optimize sensor position and orientation
Carry out reset and repeat setup
31