Table 3: Tabular overview of status signals, warnings or error messages(The described condition is reached, when Bit = 1)
Communication directions: Request byte:
 
 
 
Bit n°
 
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bit 5:
Bit 6:
Bit 7:

8 Set-up and maintenance

The safety function of the safety components must be tested. In the case of correct installation and adequate use, the
safety switchgear features maintenance-free functionality. A regular visual inspection and functional test, including the
following steps, is recommended:
1. Check fixation of the safety switch and the actuator.
2. Fitting and integrity of the cable connections.
3. The system is free of dirt and soiling (in particular metal chips).
Adequate measures must be taken to ensure protection against tampering either to prevent tampering of the safety guard, for
2
instance by means of replacement actuators.
Damaged or defective components must be replaced.
2
Response byte:
Warning/error byte:
Request byte
 
---
---
---
---
---
---
---
Error reset
from the PLC to the local safety sensor
from the local safety sensor to the PLC
from the local safety sensor to the PLC
Response byte
 
Safety output activated
Actuator detected
---
---
Input condition X1 and X2
Actuated in limit area
Error warning
Error
(enabling path switched
off)
Diagnostic
Error warning
Error output Y1
Error output Y2
Cross-wire Y1/Y2
Temperature too high
---
Internal device error
Communication error
between the field bus
Gateway and the safety
switchgear
---
Error messages
Error output Y1
Error output Y2
Cross-wire Y1/Y2
Temperature too high
Incorrect or defective
actuator
Internal device error
---
---