Mounting And Start-Up; Mounting Positions - Samson 44-2 Mounting And Operating Instructions

Table of Contents

Advertisement

Mounting and start-up

5 Mounting and start-up
NOTICE
NOTICE
!
!
Risk of overheating due to excessive ambient
temperatures or insufficient heat dissipation
when components are insulated.
− Do not include the regulator in the insula-
tion of the pipeline.
NOTICE
!
Risk of impaired functioning of the regulator
and leakage at the joint due to installation
under tension.
− Bolt the regulator to the pipeline free of
stress.
− If necessary, support the pipelines near to
the connections.
− Do not attach supports directly to the regu-
lator.
1
Shut-off valve
2
Upstream pressure gauge
3
Strainer
4
Pressure reducing valve
Downstream pressure gauge
5
Fig. 5: Pressure control with Type 44-2 (installation example)
20

5.1 Mounting positions

Install Type 44-2, Type 44-3 and Type 44-9
with the actuator housing suspended down-
ward in horizontal pipelines.
Installation conditions
Î Make sure that the regulator remains
Î Install a strainer upstream of the regula-
Î Make sure the direction of flow matches
Î Install the regulator free of stress.
Î The valves are connected to the pipeline
1
2
p
1
freely accessible after the plant has been
completed.
tor (see section 5.2).
the direction indicated by the arrow on
the body.
using threaded ends, welding ends or
flanged body.
3
4
Type 44-2 Pressure Reducing Valve
5
1
p
2
EB 2623-1 EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

44-344-9

Table of Contents