Universal excess pressure valve

Advertisement

Quick Links

Self-operated Pressure Regulators
Type 41-73 Universal Excess Pressure Valve
Type 41-73 Excess Pressure Valve
Mounting and
Operating Instructions
EB 2517 EN
Edition July 2015

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 41-73 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Samson 41-73

  • Page 1 Self-operated Pressure Regulators Type 41-73 Universal Excess Pressure Valve Type 41-73 Excess Pressure Valve Mounting and Operating Instructions EB 2517 EN Edition July 2015...
  • Page 2 Definition of signal words DANGER! NOTICE Hazardous situations which, if not Property damage message or mal- avoided, will result in death or seri- function ous injury Note:  WARNING! Additional information Hazardous situations which, if not avoided, could result in death or seri- Tip: ous injury Recommended action...
  • Page 3: Table Of Contents

    Contents General safety instructions ................4 Process medium and scope of application ............5 Transportation and storage ................5 Design and principle of operation ..............5 Installation ....................6 Assembly ......................6 Mounting position ..................8 Control line, compensation chamber and needle valve ........9 4.4 Strainer (filter)....................10 Shut-off valve ....................11 Pressure gauge ....................11 Operation ....................12 Start-up .......................12...
  • Page 4: General Safety Instructions

    General safety instructions 1 General safety instructions − The regulator is to be mounted, started up or serviced by fully trained and qualified personnel only; the accepted industry codes and practices are to be observed. Make sure employees or third persons are not exposed to any danger. − All safety instructions and warnings given in these mounting and operating instructions, particularly those concerning installation, start-up and mainte- nance, must be strictly observed.
  • Page 5: Process Medium And Scope Of Application

    Nominal pressure PN 16 to 40 · Suitable for liquids, gases and vapors up to 350 °C The valve opens when the upstream pressure rises. NOTICE The Type 41-73 Excess Pressure Valve is not a safety valve. If necessary, a suitable overpressure protection must be installed on site in the plant section. 2.1 Transportation and storage The regulator must be carefully handled, transported and stored.
  • Page 6: Installation

    Installation (5.1). The upstream pressure p is transmit- For metal bellows actuators in DN 15 to 50, ted through the compensation chamber (18) remove the crossbeam (8) from the valve. and control line (17) to the operating dia- Push the actuator stem (11) onto the spigots phragm (12) where it is converted into a po- of the bellows (5.1). Align the pillars (8.1) sitioning force. For actuator versions with a and fasten with nuts (width across flats 24, bellows, the pressure is transmitted to the op- 8.2) to the actuator (max. 60 Nm). erating bellows (12.1). The positioning force For metal bellows actuators in DN 65 to is used to move the valve plug according to 100, remove the crossbeam (8) from the the force of the positioning springs (7). The...
  • Page 7 Installation Type 41-73 Regulator · DN 32 to 100 · With balancing bellows Type 2417 Valve 12.1 Pillars turned by DN 15 to 50 90° in the drawing Type 2413 Diaphragm Actuator Actuator for DN 65 to 100 Type 2413 Actuator with metal bellows for 2 to 6 bar, 5 to 10 bar, 10 to 22 bar and 20 to 28 bar Fig. 1: Functional diagram EB 2517 EN...
  • Page 8: Mounting Position

    Installation in this position on above all the tight shut-off. request NOTICE Fig. 2: Mounting position Install a strainer (e.g. SAMSON Type 2) upstream of the regulator. NOTICE Install the excess pressure valve in horizontal Do not attach supports directly to the pipelines. On installing the valve, make sure...
  • Page 9: Control Line, Compensation Chamber And Needle Valve

    Installation 4.3 Control line, compensation Control line kit · A control line kit for tap- ping pressure directly at the valve body is chamber and needle valve available as an accessories part from SAM- Control line · A control line must be provid- SON.
  • Page 10: Strainer (Filter)

    Install the pressure gauge on the upstream side in front Needle valve · If the regulator tends to hunt, of the upstream pressure tapping point (not we recommend installing a needle valve at between the tapping point and the valve). the control line connection (16) in addition to the standard SAMSON screw joint with re- striction. EB 2517 EN...
  • Page 11: Operation

    Operation 5 Operation − All pipes conveying the process medium must be completely drained and dry. 5.1 Start-up − Air and condensate must be allowed to escape from the plant. See Fig. 1 on page 7. − Allow time for the pipes and valves to First start up the regulator after mounting all heat up.
  • Page 12: Decommissioning

    Operation Table 2: Set point adjustment – Dimension x Set point Nominal size DN range Assigned dimension x 8 to 16 bar 15 to 25 32 to 50 65 to 100 10 bar x = 89 mm x = 111 mm x = 153 mm Set point 12 bar x = 97 mm x = 122 mm x = 170 mm adjuster (6) 14 bar x =104 mm x = 133 mm x = 188 mm 4.5 to 10 bar...
  • Page 13: Cleaning And Maintenance

    Cleaning and maintenance 6 Cleaning and maintenance NOTICE Make absolutely sure that no torque See Fig. 1 on page 7. is applied to the bellows seal (5.1) The regulator does not require any mainte- during assembly or disassembly. nance. Nevertheless, it is subject to natural Otherwise, the metal bellows will be wear, particularly at the seat, plug and oper- destroyed.
  • Page 14 Cleaning and maintenance Table 3: Troubleshooting Malfunction Possible reasons Recommended action Insufficient pressure pulses on the op- Clean the control line and the screw joint with re- erating diaphragm. striction. Seat and plug worn down by deposits Disassemble the regulator and replace damaged or foreign particles. parts.
  • Page 15: Nameplate

    Nameplate 7 Nameplate Nameplates are attached to the valve and the actuator. Valve nameplate DIN version Valve type Model number with index Configuration ID (Var.-ID) Order number or date coefficient DIN version Spring force Valve size Nominal pressure Perm. differential pressure Perm. temperature Body material ANSI version ANSI version Valve size...
  • Page 16: Dimensions

    Dimensions 8 Dimensions Dimensions in mm and weights in kg Excess pressure valve Type 41-73 Nominal size DN Length L Height H1 Height H3 Standard version with rolling diaphragm Height H 0.05 to 0.25 bar Actuator ØD = 380 mm, A = 640 cm² Height H 0.1 to 0.6 bar Actuator ØD = 380 mm, A = 640 cm²...
  • Page 17: Customer Inquiries

    Customer inquiries Dimensional drawing Type 2417 Valve Type 41-73 Universal Excess Pressure Valve Type 2413 Type 2413 Diaphragm Actuator with Actuator metal bellows ØD Actuator with two diaphragms: H + 50 mm Fig. 6: Dimensions 9 Customer inquiries Contact SAMSON's After-sales Service department for support when malfunctions or defects arise. E-mail address: aftersalesservice@samson.de The addresses of SAMSON AG, its subsidiaries, representatives and service facilities world- wide can be found on the SAMSON website (u www.samson.de), in all SAMSON product catalogs or on the back of these Mounting and Operating Instructions. To assist diagnosis and in case of an unclear mounting situation, specify the following details: −...
  • Page 18: Technical Data

    Technical data 10 Technical data All pressures in bar (gauge) Valve Type 2417 Nominal pressure PN 16, 25 or 40 Nominal size DN 15 to 50 DN 65 to 80 DN 100 Max. permissible differential 16 bar 25 bar 20 bar pressure ∆p Max. permissible See pressure-temperature diagram in u T 2500 temperature Metal seal: max. 350 °C · PTFE soft seal: max. 220 °C · EPDM or FPM Valve plug soft seal: max. 150 °C · NBR soft sealing: max. 80 °C Leakage class according to Metal seal: leakage class I (≤0.05 % of K coefficient) IEC 60534-4 Soft seal: leakage class IV (≤0.01 % of K...
  • Page 19  Conversion from chromate coating to iridescent passivation We at SAMSON are converting the surface treatment of passivated steel parts in our production. As a result, you may receive a device assembled from parts that have been subjected to different surface treatment methods. This means that the surfaces of some parts show different reflections.
  • Page 20 SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 EB 2517 EN samson@samson.de · www.samson.de...