VENTING FIREPLACE - TOP (CONT'D)
NOTICE: Use flue restrictor for vertically terminated units
only. Do not use for horizontally terminated units.
(Figures 50 to 52) show the location and recommended open-
ings for the flue restrictor. Adjustments may be made for each
particular installation.
NOTICE: When installing flue restrictor, install with screws
pointing in downward position.
LP Setting - Figure 51
Natural Gas Setting - Figure 52
Page 30
Figure 50
FULL OPEN AND
FOUR INDICATED
HOLES ALIGNED
2/3 OPEN AND
TWO INDICATED
HOLES ALIGNED
Below-Grade Installation
When it is not possible to meet the required vent termination
clearances of 12 inches (305 millimeters) above grade level, a
snorkel kit is recommended. It allows installation depth down
to 7 inches (178 millimeters) below-grade level. The 7 inches
(178 millimeters) is measured from the center of the horizontal
vent pipe as it penetrates through the wall.
Observe the sidewall venting clearances. If the venting
system is installed below-grade, we recommend a window
well with adequate and proper drainage to be installed
around the termination area.
6" (152mm)
MINIMUM
PIPE STRAP
48"
(1219mm)
TYPICAL BASEMENT INSTALLATION
TYPICAL BASEMENT INSTALLATION
COMBUSTIBLE
PROJECTION
18" (457mm)
MINIMUM
12" (305mm)
ABOVE GRADE
OR EXPECTED SNOW
Figure 53
37606-4-0718