Empire Comfort Systems DVCC32BP30N-3 Installation Instructions Manual page 25

Direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

NOTICE: Cold climate installation recommendation: When
installing this unit against a non-insulated exterior wall, it must
conform to applicable codes.
VERTICAL, 90-DEGREE ELBOW WITH HORIZONTAL
TERMINATION
FINISHED WALL
(COMBUSTIBLE)
24"
TO TOP OF CHASE
FINISHED WALL
(NON-COMBUSTIBLE)
"A"
DISTANCE
TO BOTTOM
OF UNIT
A DIMENSION
DVCP32
DVCP36
DVCP42
VERTICAL, 90-DEGREE ELBOW TO HORIZONTAL OUT THE
37606-4-0718
INSTALLATION (CONT'D)
3" (76mm)
MINIMUM CLEARANCE
TO COMBUSTIBLES
12" Rise
Required
9"
BOTTOM
WALL FIRESTOP
OF FRAMING
(Inches)
57-1/2
57-1/2
59-1/8
Figure 40
WALL (12 inch minimum rise before elbow)
VENT CAP/
THIMBLE
A
6
9
12
CORNER INSTALLATION - VERTICAL, 90-DEGREE ELBOW
TO HORIZONTAL OUT THE WALL (12 inch minimum rise
before elbow)
DIM.
A
90° ELBOW
WALL FIRESTOP/
THIMBLE
"C"
"B"
B
(Inches)
11-1/4 to 12-3/4
14-1/4 to 15-3/4
17-1/4 to 18-3/4
Figure 41
"A"
DVCP32
DVCP36
(Inches)
12-3/4
13-3/4
Figure 42
"A"
PIPE
LENGTH
VENT CAP
C
4-3/4 to 6-1/4
7-3/4 to 9-1/4
10-3/4 to 12-1/4
WALL FIRESTOP/
THIMBLE
6" (152 mm)
MINIMUM
VENT
CAP
9" (229 mm)
MINIMUM
DVCP42
15-15/16
Page 25