Line differential protection RED670 2.0
Product version: 2.0
Station communication
Table 110. Communication protocols
Function
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Table 111. IEC 61850-9-2 communication protocol
Function
Protocol
Communication speed for the IEDs
Table 112. LON communication protocol
Function
Protocol
Communication speed
Table 113. SPA communication protocol
Function
Protocol
Communication speed
Slave number
Table 114. IEC 60870-5-103 communication protocol
Function
Protocol
Communication speed
Table 115. SLM – LON port
Quantity
Optical connector
Fiber, optical budget
Fiber diameter
*) depending on optical budget calculation
ABB
Value
IEC 61850-8-1
100BASE-FX
IEC 60870–5–103
9600 or 19200 Bd
DNP3.0
300–19200 Bd
TCP/IP, Ethernet
100 Mbit/s
Value
IEC 61850-9-2
100BASE-FX
Value
LON
1.25 Mbit/s
Value
SPA
300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
1 to 899
Value
IEC 60870-5-103
9600, 19200 Bd
Range or value
Glass fiber: type ST
Plastic fiber: type HFBR snap-in
Glass fiber: 11 dB (1000m/3000 ft typically *)
Plastic fiber: 7 dB (10m/35ft typically *)
Glass fiber: 62.5/125 mm
Plastic fiber: 1 mm