ABB Relion 670 Series Product Manual page 90

Line differential protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Line differential protection RED670 2.0
Product version: 2.0
Logic
Table 88. Tripping logic common 3-phase output SMPPTRC
Function
Trip action
Minimum trip pulse length
3-pole trip delay
Single phase delay, two phase
delay and evolving fault delay
Table 89. Configurable logic blocks
Logic block
Quantity with cycle time
fast
LogicAND
60
LogicOR
60
LogicXOR
10
LogicInverter
30
LogicSRMemory
10
LogicRSMemory
10
LogicGate
10
LogicTimer
10
LogicPulseTimer
10
LogicTimerSet
10
LogicLoopDelay
10
Trip Matrix Logic
6
Boolean 16 to Integer
4
Boolean 16 to integer
4
with Logic Node
Integer to Boolean 16
4
Integer to Boolean 16
4
with Logic Node
90
Range or value
3-ph, 1/3-ph, 1/2/3-ph
(0.000-60.000) s
(0.020-0.500) s
(0.000-60.000) s
Range or value
medium
normal
60
160
-
60
160
-
10
20
-
30
80
-
10
20
-
10
20
-
10
20
-
10
20
(0.000–90000.000) s
10
20
(0.000–90000.000) s
10
20
(0.000–90000.000) s
10
20
(0.000–90000.000) s
6
-
-
4
8
-
4
8
-
4
8
-
4
8
-
Accuracy
-
± 0.2% or ± 30 ms whichever is greater
± 0.2% or ±10 ms whichever is greater
± 0.2% or ±10 ms whichever is greater
1MRK505310-BEN C
Accuracy
-
-
-
-
-
-
-
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
-
-
-
-
-
ABB