ABB Relion 670 Series Product Manual page 81

Line differential protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Line differential protection RED670 2.0
Product version: 2.0
Table 69. Fuse failure supervision VDSPVC
Function
Operate value, block of main fuse
failure
Reset ratio
Operate time, block of main fuse
failure at 1 to 0 x U
r
Reset time, block of main fuse
failure at 0 to 1 x U
r
Operate value, alarm for pilot fuse
failure
Reset ratio
Operate time, alarm for pilot fuse
failure at 1 to 0 x U
r
Reset time, alarm for pilot fuse
failure at 0 to 1 x U
r
ABB
Range or value
(10.0-80.0)% of UBase
<110%
Min. = 5 ms
Max. = 15 ms
Min. = 15 ms
Max. = 30 ms
(10.0-80.0)% of UBase
<110%
Min. = 5 ms
Max. = 15 ms
Min. = 15 ms
Max. = 30 ms
Accuracy
±0.5% of Ur
±0.5% of Ur
1MRK505310-BEN C
81