Omron CP2E Manual page 21

Micro plc designed to support data collection and machine to machine communication
Table of Contents

Advertisement

■ Approved Standards
Item
Safety standards
EMC
(See note.)
Note: EMC conforms to EN 61131-2 clause 8 except in the following cases.
• When Expansion I/O Units with DC inputs are connected to a CPU Unit with an AC power supply, the burst immunity between power
supplies will be 1 kv.
• When the signal wire for transistor outputs exceeds 10 m, the surge immunity of DC output signal lines will not conform.
■ Input Specifications
CPU Units
AC Inputs (Not Isolated)
Item
Input voltage
Input impedance
Input current
ON voltage
OFF voltage
ON response time
OFF response time
Note: Can be selected using the filter settings.
DC Inputs: I0 to I3 for Units with 10 I/O points, I0 to I9 for Units with 20 I/O Points (Not Isolated)
Item
Input voltage
Input impedance
Input current
ON voltage
OFF voltage
ON response time
OFF response time
Note: Can be selected using the input filter settings, except when I0 is being used for an 8-digit counter with a high-speed input.
cULus: UL508/CSA C22.2 No.142 (ZEN-PA03024 take Class I Div2)
Conforms to EN/IEC 61131-2 clause 11, excluding 11.7.2.2 (Overvoltage category 2 and Pollution degree II
conforms to IEC 60664-1)
Radiation Field Emission
Noise Terminal Voltage Emission
Electrostatic Discharge Immunity
Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
Immunity to Conducted Disturbances Induced by Radio-frequency Fields
Momentary Power Interruption Immunity
Specifications
100 to 240 VAC +10%, −15%, 50/60 Hz
680 kΩ
0.15 mA/100 VAC, 0.35 mA/240 VAC
80 VAC min.
25 VAC max.
50 ms or 70 ms at 100 VAC (See note.)
100 ms or 120 ms at 240 VAC (See note.)
Specifications
12 to 24 VDC +20%, −10%
5.3 kΩ
4.5 mA (typ.)/24 VDC
8 VDC min.
5 VDC max.
15 ms or 50 ms (See note.)
Specification
CISPR11
Class A, Group 1
CISPR11
Class A, Group 1
IEC61000-4-2
In air: 8 kV, In contact: 6 kV
IEC61000-4-3
10 V/m
IEC61000-4-4
Power line
AC I/O: 2 kV
DC I/O: 1 kV
IEC61000-4-5
Normal Noise
AC power supply, AC I/O: 1 kV
DC power supply, DC I/O: 0.5 kV
Common Noise
AC power supply, AC I/O: 2 kV
DC power supply: 1 kV
DC I/O: 0.5 kV
IEC61000-4-6
3 V
IEC61131-2
CPU Units with AC Power Supplies:
10 ms max.
CPU Units with DC Power Supplies:
2 ms max. (level: PS1)
Circuit drawing
IN
IN
100 to 240 VAC
N
L
Circuit drawing
IN
5.1 kΩ 1.8 kΩ
IN
12 to 24 VDC
COM
ZEN V2 Units
330 kΩ 300 kΩ
Internal
51 kΩ
circuit
Internal
circuit
9