Toshiba MMY-MAP1004HT5P Service Manual page 165

Hide thumbs Also See for MMY-MAP1004HT5P:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Sub-code
F
1
2
F
1
5
F
1
6
F
2
2
F
2
3
F
2
4
F
3
1
H05
H06
H
0
7
01: TK1 sensor error
02: TK2 sensor error
H08
03: TK3 sensor error
04: TK4 sensor error
05: TK5 sensor error
H15
01: TK1 oil circuit error
02: TK2 oil circuit error
H16
03: TK3 oil circuit error
04: TK4 oil circuit error
05: TK5 oil circuit error
H25
L
0
4
Number of priority indoor units
L06
(check code L05 or L06 depending
on individual unit)
L
0
8
L
1
0
L
1
7
L
1
8
L
2
8
Display of receiving unit
TCC-LINK
Indicator light block
central control
or main remote
Operation Timer Ready
Flash
controller
display
F
1
2
A
F
1
5
A
F
1
6
A
F
2
2
A
F
2
3
A
F
2
4
A
F
3
1
I S
H05
H06
H
0
7
H08
H15
H16
H25
L
0
4
I S
L
0
5
I S
L
0
6
I S
L (
0
) 8
I S
L
1
0
I S
L
1
7
I S
L
1
8
I S
L
2
8
I S
– 164 –
Typical fault site
Outdoor suction
Outdoor suction temperature sensor (TS1) has
L
T
temperature sensor (TS1)
been open/short-circuited.
error
Outdoor temperature
Wiring error in outdoor temperature sensors (TE1,
L
T
sensor (TE1, TL) wiring
TL) has been detected.
error
Outdoor pressure sensor
Wiring error in outdoor pressure sensors (Pd, Ps)
L
T
(Pd, Ps) wiring error
has been detected.
Outdoor discharge
Outdoor discharge temperature sensor (TD3) has
L
T
temperature sensor (TD3)
been open/short-circuited.
error
Low pressure sensor (Ps)
L
T
Output voltage of low pressure sensor (Ps) is zero.
error
Output voltage of high pressure sensor (Pd) is zero
High pressure sensor (Pd)
L
T
or provides abnormal readings when compressors
error
have been turned off.
Outdoor EEPROM is faulty (alarm and shutdown
M
O
u
d t
o
r o
E
E
P
R
O
M
e
r r
r o
for header unit and continued operation for follower
unit)
Outdoor discharge
Wiring/installation error or detachment of outdoor
temperature sensor (TD1)
discharge temperature sensor (TD1) has been
wiring error
detected.
Activation of low-pressure
Low pressure (Ps) sensor detects abnormally low
protection
operating pressure.
Temperature sensor for oil level detection (TK1-5)
L
o
w
l i o
e l
v
l e
p
o r
e t
t c
o i
n
detects abnormally low oil level.
Error in temperature
Temperature sensor for oil level detection (TK1-5)
sensor for oil level
has been open/short-circuited.
detection (TK1-5)
Outdoor discharge
Wiring/installation error or detachment of outdoor
temperature sensor (TD2)
discharge temperature sensor (TD2) has been
wiring error
detected.
No temperature change is detected by
Oil level detection circuit
temperature sensor for oil level detection (TK1-5)
error
despite compressor having been started.
Outdoor discharge
Wiring/installation error or detachment of outdoor
temperature sensor (TD3)
discharge temperature sensor (TD3) has been
wiring error
detected.
Identical refrigerant line address has been
Duplicated outdoor
M
assigned to outdoor units belonging to different
refrigerant line address
refrigerant piping systems.
Duplicated priority indoor
More than one indoor unit has been set up as
M
unit (as displayed on
priority indoor unit.
priority indoor unit)
Duplicated priority indoor
unit (as displayed on
More than one indoor unit has been set up as
M
indoor unit other than
priority indoor unit.
priority indoor unit)
Indoor group address not
Address setting has not been performed for one or
M
set
more indoor units (also detected at indoor end).
Outdoor unit capacity has not been set (after P.C.
M
O
u
d t
o
r o
c
a
p
a
c
y t i
n
t o
s
t e
board replacement).
Outdoor model
Old model outdoor unit (prior to 3 series) has been
M
incompatibility error
connected.
Cooling/heating selection
Cooling/heating cycle error resulting from piping
M
unit error
error is detected.
Too many outdoor units
More than four outdoor units have been
M
connected
connected.
Description of error

Hide quick links: