Toshiba MMY-MAP1004HT5P Service Manual page 149

Hide thumbs Also See for MMY-MAP1004HT5P:
Table of Contents

Advertisement

(4) Individual start/stop (ON/OFF) individual test operation function
This function is provided to start/stop (ON/OFF) individually each indoor unit connected to the same system by
using switches on the interface board of the header unit.
Set SW01 [16] and set SW02, SW03 to indoor address No. (1 to 64) to be started (Refer to the following table*) -
only the setup indoor unit starts operation.
(In the rotary switches of the indoor unit which operates in a group by the remote controller, the follower unit cannot
be individually started or stopped. In this case, [ - - ] is displayed on 7-segment display [B] on the interface P.C.
board of the header unit.)
<Operation procedure>
0
Power ON
Set up the operation mode of the remote controller.
(If it is not set up, the operation continues with the
current mode.)
Match the rotary
(7-segment display)
switches on the
[A]
interface P.C.
[
board of the
header unit to the
Address display
of corresponding
following table*.
indoor unit
Press the push-switch SW04 on the same board for 2
seconds or more.
(If pressed continuously for 10 seconds or more, the
operation changes to the individual test operation.)
The indoor unit to be started operates.
Press the push-switch SW05
on the interface P.C. board of
the header unit for 2 seconds
or more.
After test operation, return the display select switches
SW01/SW02/SW03 on the interface P.C. board of the
header unit to [1/1/1].
NOTE)
The individual test operation returns to the normal operation after 60 minutes.
Be sure to turn on power at the indoor side
before power-ON of outdoor unit.
[B]
]
[
]
[ 00] is displayed
for 5 seconds after
operation-ON.
Operation check
If the discharge temperature does not change
though COOL or HEAT has been set up from the
remote controller, misconnection is considered.
(7-segment display)
[A]
[B]
[
]
[
Address display
[ 00] is displayed
of corresponding
for 5 seconds after
indoor unit
operation-ON.
If an error is already displayed with SW01/SW02/SW03
being [1/1/1], return the status to normal one according
to troubleshooting and then execute a test operation.
The unit which is not given with priority by heating
priority control, cooling priority control, and selection
of cooling or heating mode is not operated.
In this case, "
operation ready" or "
mode controlled" is displayed on the remote controller.
(7-segment display)
[A]
[
]
Address display
[ 11] is displayed for 5 seconds after operation-ON.
of corresponding
(For individual test operation, [ FF] is displayed.)
indoor unit
*
SW01
SW02
]
16
1~16
16
1~16
16
1~16
End
16
1~16
– 148 –
operation
7-segment display [A]
7-segment display [B]
SW04
SW05
SW01
SW02
SW03
<Rotary switches>
[B]
[
]
SW03
Units to be operated
Address 1 to
1
Address 16 }
individually
Address 17 to
2
Address 32 }
individually
Address 33 to
3
Address 48 }
individually
Address 49 to
4
Address 64 }
individually
Start
In individual
start/stop